66 Using AMS Device Manager to configure the meter
Section 4: Configuring a 3818 LNG Meter Daniel 3818 LNG Liquid Ultrasonic Meter Installation Manual
May 2012 3-9000-771 Rev A
4. After all of the data shown below is entered, click Apply to write the parameters to the
meter.
a. Click the
Frequency/Digital Outputs tab to configure Frequency/Digital Output 1,
2 and 3 Source and drive Mode. Select the Source for each Frequency/Digital
output and select the desired drive Mode. The Mode options are Open Collector
which requires an external excitation voltage and pull-up resistor or TTL mode
which outputs a 0-5 VDC signal (each Frequency output has an A and B output
phase). (Refresh Note: If changes are made to any Source variable on this page,
apply the changes and navigate to the Guided Setup page. Navigate back to the
Manual Setup for the changes to be reflected in other Manual Setup pages).
b. Click the
Frequency and Digital Output 1 tab to configure the Content, (flow)
Direction, Channel B Phase frequency output, Lag forward, Lead Reverse or Lead
Forward, Lag Reverse (Phase B lags Phase A while reporting forward flow and lead
Phase A while reporting reverse flow or the opposite), Digital Output 1 Channel A
Content and Polarity, Channel B Content and Polarity, Maximum Frequency, and
Lower and Upper Range Units of Measure.
c. Click the
Frequency and Digital Output 2 tab and repeat Step 3b to configure
Frequency and Digital Output 2 parameters.
5. Click
Setup HART to configure the HART parameters (tag, date, descriptor, message
text, Final Assembly number, Poll address and number of response preambles are
displayed). After all of the data is entered click Apply to write the parameters to the
meter.
6. From the AMS Device Manager Overview page, click
Zero Flow Meter. Set the low flow
volume threshold cutoff. If the average flow velocity for a batch is below this value, the
volume accumulated is set to zero.
Figure 4-7 AMS Device Manager - Zero Flow