Desa CD36TN-M Indoor Fireplace User Manual


 
www.desatech.com
118531-01A 13
H
V
GROUND FLOOR INSTALLATION
Recommended CHVK-58 Corner Horizontal
Vent Kit:
Installation using cabinet surrounds
Through the wall using square termination
(up to 24" horizontal pipe)
Corner installation (Using one 6" vertical sec-
tion, one 90° elbow and a maximum of 24" of
horizontal pipe)
VENTING INSTALLATION
INSTRUCTIONS
Continued
Figure 14 - Horizontal Termination
Conguration For Corner Installation
Using One 90° Elbow
Figure 15 - Horizontal Termination
Conguration with Vertical Rise and One
90° Elbow






51" 6" 26" Max.
57
1
/
4
" Min. 1' 30" Max.
69
1
/
4
" Min. 2' 74" Max.
81
1
/
2
" Min. 3' 98" Max.
94" Min. 4' 122" Max.
106" Min. 5' 146" Max.
159" Min. 9' 20' Max.
TO
H
Wall
Firestop
Straight/
Adjustable
Pipe 24" Max.
Horizontal
Square
Termination
90°
Elbow
Corner Installation
 
51" Min. 32
1
/
2
" Max
90° Elbow
Wall
Firestop
Square
Termination
Not to Exceed
(H) Limits
As
Required
for (V),
See Chart
for Pipe
Section
Required

Figures 14 through 18 show different congura-
tions and alternatives for venting with horizontal
termination. Each figure includes a chart with
critical minimum and maximum dimensions which
MUST be met. IMPORTANT: Remember that a
horizontal run of venting must have a 1/4" rise for
every 12" of run toward the termination.
Figure 16 - Square Termination
Clearance at Ground Floor Installation
12"
Min.