Eclipse Combustion 5600 Burner User Manual


 
40
Eclipse Veri-Flame Instruction Manual 818-2/02
Hold Flame signal—actual, induced, or runaway scanner—is detected be-
fore start-up or after shutdown. The fan is energized. If the cause is
corrected within 30 seconds, as in afterburn, the control will turn
off the fan and continue the sequence.
Lockout Same conditions as above, except the cause has not been corrected
within 30 seconds, resulting in a lockout and the alarm being energized.
Hold For purge & modulation models: Flame signal—actual, induced,
or runaway scanner—is detected during the selected purge time
period. The fan is energized. If the cause is corrected within 30 sec-
onds, as in afterburn, the control will turn off the fan and continue
the sequence.
Lockout For purge & modulation models: Same conditions as above,
except the cause has not been corrected within 30 seconds, resulting
in a lockout and the alarm being energized.
Lockout Internal control failure; replace controller.
Lockout Internal control failure; replace controller.
Status In combination with other messages, shows the control is in the
minimum pilot test mode.
MESSAGE TYPE EXPLANATION
Table 9.2
Remote Display Diagnostic Messages (continued)
UNSAFE FLAME ON
XX:XX:XX LOCKOUT
UNSAFE–FLM–PURGE
XX:XX:XX LOCKOUT
V–INTERNAL FAULT
XX:XX:XX LOCKOUT
WATCHDOG FAIL
XX:XX:XX LOCKOUT
XXXXXXX
XXXXXTESTXX
UNSAFE–FLM–PURGE
UNSAFE FLAME ON