36
Eclipse Veri-Flame Instruction Manual 818-2/02
Table 9.1
Veri-Flame Operating Sequence (continued)
BURNER START-UP (continued)
Is flame signal present?
NO
Modulator sent to automatic 20
seconds after main valve is
energized.
Pilot will shut off 10 seconds
after main flame is energized.
Main flame of burner is proven.
Flame signal = XX.XVolts DC;
elapsed time is shown in hours:
minutes:seconds.
YES
ERROR MESSAGE
MAIN FLAME FAIL
XX:XX:XX LOCKOUT
AUTOMATIC
MODULATION
NORMAL MESSAGE
NORMAL MESSAGE
BURNER ON XX.XV
TIME = XXXX:XX:XX
IF Interrupted Pilot is selected IF Intermittent Pilot Is Selected
NORMAL MESSAGE
MAIN FLAME ON
PILOT OFF
NORMAL MESSAGE
MAIN FLAME ON
NORMAL MESSAGE
MAIN FLAME ON
MODULATION MODELS
PURGE & NO PURGE MODELS
MODULATION MODELS
PURGE & NO PURGE MODELS
Is flame signal present?
NO
YES
Is air switch signal on?
NO
YES
Is recycle selected?
NO
YES
Is recycle selected?
Was the main flame on more
than 35 seconds?
NO
YES
MAIN FLAME FAIL
RECYCLING
ERROR MESSAGE
MAIN FLAME FAIL
XX:XX:XX LOCKOUT
ERROR MESSAGE
Unit returns to beginning
sequence.
NO
YES
Was the main flame on more
than 35 seconds?
NO
YES
AIR FAILURE
RECYCLING
ERROR MESSAGE
AIR FAILURE
XX:XX:XX LOCKOUT
ERROR MESSAGE
Unit returns to beginning
sequence.