Eclipse Combustion 5600 Burner User Manual


 
32
Eclipse Veri-Flame Instruction Manual 818-2/02
Table 8.3
LED Status & Conditions for Veri-Flame Modulation Models
Modulation Model
LED(S) LIT POSSIBLE CAUSES
SYSTEM ERROR 1) The flame detected is out of sequence, flame signal light is on.
2) The sensor is “runaway”, flame signal light is on.
3) Inductance is detected on sensor wires, flame signal light is on.
4) Voltage wired into terminals 3, 4 or 5.
5) Internal relay contacts welded.
6) Internal controller failure.
7) Air flow switch closed before start-up.
8) High purge damper switch and/or main fuel valve switch opens during start-up.
9) Low fire switch not made before TFI.
1) Pilot flame is not established in selected TFI.
2) Main flame is not established in selected TFI.
3) Main flame fails within 35 seconds of TFI.
4) Flame failed during operation in non-recycle mode.
5) Flame failed 35 seconds after TFI and was not established after try in recycle mode.
1) Burner in run mode, firing rate determined by automatic controller (normal operation).
1) Purge high sequence (normal operation).
1) Purge low sequence (normal operation).
FLAME FAILURE
INTERLOCKS CLOSED and
LOW FIRE
INTERLOCKS CLOSED and
AUTO
INTERLOCKS CLOSED
and HIGH FIRE
AIR FAILURE
1) Air flow switch not closed within ten seconds of start-up.
2) Air flow switch is open during timing cycle.
3) Air flow switch is open during firing cycle.
INTERLOCKS CLOSED 1) The interlocks are closed (normal operation), power on terminal 7.