Eclipse Combustion 5600 Burner User Manual


 
30
Eclipse Veri-Flame Instruction Manual 818-2/02
LED STATUS
This section describes the status of operating conditions based on the LED or
combination of LEDs which are lit on the front cover of each Veri-Flame model.
Table 8.1
LED Status & Conditions for Veri-Flame No Purge Models
LED(S) LIT POSSIBLE CAUSES
INTERLOCKS CLOSED
SYSTEM ERROR
1) The interlocks are closed (normal operation), power on terminal 7.
1) The flame detected is out of sequence, flame signal light is on.
2) The sensor is “runaway”, flame signal light is on.
3) Inductance is detected on sensor wires, flame signal light is on.
4) Voltage wired into terminals 3, 4 or 5.
5) Internal relay contacts welded.
6) Internal controller failure.
FLAME FAILURE
1) Pilot flame is not established in selected TFI.
2) Main flame is not established in selected TFI.
3) Main flame fails within 35 seconds of TFI.
4) Flame failed during operation in non-recycle mode.
5) Flame failed 35 seconds after TFI and was not established after try in recycle mode.
7) Main valve closed switch defective, no power to V.
No Purge Model