Eclipse Combustion 5600 Burner User Manual


 
31
Eclipse Veri-Flame Instruction Manual 818-2/02
Table 8.2
LED Status & Conditions for Veri-Flame Purge Models
LED(S) LIT POSSIBLE CAUSES
INTERLOCKS CLOSED
SYSTEM ERROR
1) The interlocks are closed (normal operation), power on terminal 7.
1) The flame detected is out of sequence, flame signal light is on.
2) The sensor is “runaway”, flame signal light is on.
3) Inductance is detected on sensor wires, flame signal light is on.
4) Voltage wired into terminals 3, 4 or 5.
5) Internal relay contacts welded.
6) Internal controller failure.
7) Air flow switch closed before start-up.
8) Main fuel valve switch opens after shutdown or before start-up, no power to V.
1) Pilot flame is not established in selected TFI.
2) Main flame is not established in selected TFI.
3) Main flame fails within 35 seconds of TFI.
4) Flame failed during operation in non-recycle mode.
5) Flame failed 35 seconds after TFI and was not established after one try in recycle mode.
1) Air flow switch not closed within ten seconds of start-up.
2) Air flow switch is open during timing cycle.
3) Air flow switch is open during firing cycle.
FLAME FAILURE
AIR FAILURE
Purge Model