Carrier 48TC*D08 Air Conditioner User Manual


 
9
1/2-20 UNF RH
30
0.596
.47
5/8” HEX
SEAT
CORE
WASHER
DEPRESSOR PER ARI 720
+.01/-.035
FROM FACE OF BODY
7/16-20 UNF RH
O-RING
45
torqued into the seat. Appropriate handling is
required to not scratch or dent the surface.
1/2" HEX
This surface provides a metal to metal seal when
o
o
(Part No. EC39EZ067)
C08453
Fig. 9 -- CoreMax Access Port Assembly
EXAMPLE:
Model 48TC*D14
Circuit A:
Outdoor Temperature 85_F(29_C)..................
Suction Pressure 125 psig (860 kPa).................
Suction Temperature should be 58_F(14_C)..........
Circuit B:
Outdoor Temperature 85_F(29_C)..................
Suction Pressure 120 psig (830 kPa).................
Suction Temperature should be 60_F(16_C)..........
48TC