Carrier 48TC*D08 Air Conditioner User Manual


 
8
5. Finned surfaces should remain wet with cleaning
solution for 10 minutes.
6. Ensure surfaces are not allowed to dry before rinsing.
Reapply cleaner as needed to ensure 10--minute satur-
ation is achieved.
7. Thoroghly rinse all surfaces with low velocity clean
water using downward rinsing motion of water spray
nozzle. Protect fins from damage from the spray
nozzle.
Evaporator Coil Metering
Devices
The metering devices are multiple fixed--bore devices
(Acutrolt) swaged into the horizontal outlet tubes from
the liquid header, located at the entrance to each
evaporator coil circuit path. These are non--adjustable.
Service requires replacing the entire liquid header
assembly.
To check for possible blockage of one or more of these
metering devices, disconnect the supply fan contactor
(IFC) coil, then start the compressor and observe the
frosting pattern on the face of the evaporator coil. A frost
pattern should de velop uniformly across the face of the
coil starting at each horizontal header tube. Failure to
devel op frost at an outlet tube can indicate a plugged or a
missing orifice.
Refrigerant System Pressure Access Ports
There are two access ports in the system -- on the suction
tube near the compressor and on the discharge tube near
the compressor. These a re brass fittings with black plastic
caps. The hose connection fittings are standard 1/4 SAE
male flare coupl ings.
The brass fittings are two--piece High Flow valves, with a
receptacle base brazed to the tubing and an integral
spring-closed check valve core screwed into the base. (See
Fig. 9.) This check valve is permanently assembled into
this core body and cannot be serviced separately; replace
the entire core body if necessary. Service tools are
available from RCD that allow the replacement of the
chec k valve core without having to recover the entire
system refrigerant charge. Apply compressor re frigerant
oil to the check valve core’s bottom O-ring. Install the
fitting body with 96 +/-- 10 in-lbs of torque; do not
overtighten.
PURONR (R--410A) REFRIGERANT
This unit is designed for use with Puron (R--410A)
refrigerant. Do not use any other refrigerant in this
system.
Puron (R--410A) refrigerant is provided in pink (rose)
colored cylinders. These cylinders a re available with and
without dip tubes; cylinders with dip tubes will have a
labe l indicating this feature. For a cylinder with a di p
tube, place the cylinder in the upright position (access
valve at the top) when removing liquid refrigerant for
charging. For a cylinder without a dip tube, invert the
cylinder (access valve on the bottom) when removing
liquid refrigerant.
Because Puron (R--410A) refrigerant is a blend, it is
strongly rec ommended that refrigerant always be removed
from the cylinder as a liquid. Admit liquid refrigerant into
the system in the discharge line. If adding refrigerant into
the suction line, use a commercial metering/expansion
devic e a t the gauge manifold; remove liquid from the
cylinder, pass it through the metering device at the gauge
set and then pass it into the suction line as a vapor. Do not
remove Puron (R--410A) refrigerant from the cylinder a s a
vapor.
Refrigerant Charge
Amount of refri gerant charge is listed on the uni t’s
nameplate. Refer to Carrier GTAC2--5 Charging,
Recovery, Recycling and Reclamation training manual
and the following procedures.
Unit panels must be in pla ce when unit is operating during
the charging procedure. To prepare the unit for charge
adjustment.
No
Charge
Use standard evacuating techniques. After evacuating
system, weigh in the specified amount of refrigerant.
Low--Charge
Cooling
Using Cooling Charging Charts (Figs. 10, 11, 12, and 13),
vary re frigerant until the conditions of the appropriate
chart are met. Note the charging charts are different from
the type normally used. Charts are based on charging the
units to the correct superheat for the various operating
conditions. Accurate pressure gauge and temperature
sensing device are required. Connect the pressure gauge to
the service port on the suction line. Mount the temperature
sensing device on the suction line and insulate it so that
outdoor ambient temperature does not affect the reading.
Indoor--air cfm must be within the normal operating range
of the unit.
To Use Cooling Charging
Charts
Select the appropriate unit charging chart from Figs. 10,
11, 12, and 13.
S Sizes D08 and D12 each have one cooling charging chart
S Size D14 has two cooling charging charts: Circuit A and
Circuit B
Take the outdoor ambient temperature and read the
suction pressure gauge. Refer to chart to determine what
suction temperature should be. If suction temperature is
high, add refrigerant. If suction temperature is low,
carefully recover some of the charge. Recheck the suction
pressure as charge is adjusted.
For D14 size, perform this procedure once for Circuit A
(using the Circuit A chart) and once for Circuit B (using
the Circuit B chart).
48TC