Carrier 48TC*D08 Air Conditioner User Manual


 
51
SW3 Protocol Selection
PROTOCOL DS8 DS7 DS6 DS5 DS4 DS3 DS2 DS1
BACnet MS/TP
(Master)
Unused OFF OFF OFF ON OFF Select Baud Select Baud
Modbus
(Slave)
Unused OFF OFF ON ON OFF Select Baud Select Baud
N2
(Slave)
Unused OFF OFF OFF ON ON OFF OFF
LonWorks Unused ON ON OFF ON OFF OFF OFF
NOTE:
DS = Dip Switch
BACnet MS/TP SW3 example shown
Baud Rate Selections
BAUD RATE DS2 DS1
9600 OFF OFF
19,200 ON OFF
38,400 OFF ON
76,800 ON ON
C07166
Fig. 68 -- RTU--MP SW3 Dip Switch Settings
BACnet
MS/TP
BACnet Master Slave/Token Passing (MS/TP) is used for
communicating BACnet over a sub--network of
BACnet--only controllers. This is the default Carrier
communications protocol. Each RTU--MP module acts as
an MS/TP Master. The speed of an MS/TP network can
range from 9600 to 76.8K baud. Physical Addresses can
be set from 01 to 99.
Modbus
The RTU--MP module can speak the Modicon Modbus
RTU Protocol as described in the Modicon Modbus
Protocol Referenc e Guide, PI--MBUS--300 Rev. J. The
speed of a Modbus network can range from 9600 to 76.8K
baud. Physical Addresses can be set from 01 to 99.
Johnson
N2
N2 i s not a standard protocol, but one that was created by
Johnson Controls, Inc. that has been made open and
avai lable to the publ ic. The speed of N2 network is
limited to only 9600 baud. Physical Addresses can be set
from 01 to 99.
LonW
orks
LonWorks is an open protocol that requires the use of
Eche lon’s Neuron microprocessor to encode and decode
the LonWorks packets. In order to reduce the cost of
adding that hardware on every module, a separate
LonWorks Option Card (LON--OC) was designed to
connect to the RTU--MP.
This accessory card is needed for LonWorks and has to be
ordered and connected using the ribbon cable to plug J15.
The RTU--MP’s baud rate must be set to 38.4k to
communicate wit h the LON--OC. The address switche s
(SW1 & SW2) are not used with LonWorks.
Local
Access
BACview
6
Handheld
The BACview
6
is a keypad/display interface used to
connect to the RTU--MP to access the control information,
read sensor values, and test the RTU, see Fig. 69. This is
an accessory interface that does not come with the MP
controller and can only be used at the unit. Connect the
BACview
6
to the RTU--MP’s J12 local access port. There
are 2 password protected levels in the display (User and
Admin). The user password defaults to 0000 but can be
changed. The Admin password is 1111 and cannot be
change d. There i s a 10 minute auto logout if a screen is
left idle. See RTU--MP Controls, Start--Up, Operation, and
Troubleshooting Instructions (Form 48--50H--T--2T),
Appendix A for navigation and screen content.
Virtual BACview
Virtual BACview is a freeware computer program that
functions as the BACview
6
Handheld. The USB Link
interface (USB-- L) is required to connect a computer to
the RTU--MP board. The link cable connects a USB port
to the J12 local access port. This program functions and
operates identi cal t o the handheld.
RTU--MP Troubleshooting
Communication LEDs
The LEDs indicate if the cont roller is speaking to the
devic es on the net work. The LEDs should reflect
communication traffic based on the baud rate set. The
higher t he baud rate the more solid the LEDs will appear.
48TC