EXAMPLES OF GUIDELINE USE — Figure 29 shows an incorrect application. Figure 30 shows the corrected layout.
An incorrect application:
1. RoomA & B units are on the same controller but on different duct
air series.
2. Room B calls for half the cfm as in units in roomA — not feasible
because there is only one controller.
3. Units in room C are on different duct runs with one control — not
correct.
4. Units in room D are fine for one control, but controller should be
on second unit in air series.
Fig. 29 — Incorrect Layout of Modulineா Units with Controls
39