A.O. Smith HW 610 Boiler User Manual


 
39
WARNING
After placing boiler into operation, the ignition system safety shutoff
device must be tested by the following test method.
1. Reset High Limit Temperature Control to lowest setting.
(See gure 2 on page 8).
2. Reset System Controller to maximum setting, causing a call for heat
and allowing unit to run until High Limit Temperature Control trips.
3. Resetting the High Limit Temperature Control to a higher setting,
unit should run.
4. Reset System Controller and High Limit Temperature Control to
desired temperature. If unit fails to run, see Trouble-Shooting in
this manual.
Before operating the boiler, the entire system must be lled with
water, purged of air and checked for leaks. Do not use Stop Leak
or other boiler compounds. The gas piping should also be leak
tested.
Any safety devices including low water cutoffs used in conjunction
with this boiler should receive periodic (every six months) inspection
to assure proper operation. A low water cutoff device of the oat
type should be ushed every six months. All relief valves should be
inspected and manually operated at least twice a year.
IMPORTANT
IT IS RECOMMENDED THAT A QUALIFIED PERSON PERFORM
THE INITIAL FIRING OF THE BOILER. AT THIS TIME THE
USER SHOULD NOT HESITATE TO ASK THE INDIVIDUAL
ANY QUESTIONS WHICH HE MAY HAVE IN REGARD TO THE
OPERATION AND MAINTENANCE OF THE UNIT.
FILLING THE SYSTEM
1. Fast ll system through bypass until pressure approaches
desired system pressure. Close bypass valve and permit
pressure to be established by the pressure reducing valve.
2. Vent all high points in system to purge system of air.
If pressure bleeding of system is desired, install valves as shown in
Figure 7 on page 14.
Where cast iron radiation and motorized valves are used, conventional
system pressure and installation practices should be followed.
Provisions should be made to permit manual venting of radiators
or convectors.
PRECAUTIONS
If the unit is exposed to the following, do not operate boiler until all
corrective steps have been made by a qualied serviceman:
1. Flooding to level of burner or controls or higher.
2. Exposure to re.
3. If damaged.
4. Firing without water.
5. Sooting.
CAUTION
SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY
FAIL TO SHUT OFF, DO NOT TURN OFF OR DISCONNECT
THE ELECTRICAL SUPPLY TO THE PUMP. INSTEAD,
SHUTOFF THE GAS SUPPLY AT A LOCATION EXTERNAL TO
THE APPLIANCE.
PILOT AND MAIN BURNER
To maintain safe operation of the boiler, check the pilot and the main
burner once every six months for proper ame characteristics.
1. MAIN BURNER
The main burner, Figure 34, should display the following
characteristics:
Provide complete combustion of gas.
Cause rapid ignition and carryover of ame across entire burner.
Give reasonably quiet operation during ignition, burning and
extinction.
Cause no excessive lifting of ame from burner ports.
If the proceeding burner characteristics are not evident, check for
accumulation of lint or other foreign material that restricts or blocks
the air openings to the burner or boiler.
Also check for good ow of combustion and ventilating air to the unit.
Maintain a clear area around the boiler at all times.
FIGURE 34.
The boiler should be periodically inspected by a qualied servicer
for continuous safe operation.
Qualied servicers should follow this procedure when the boiler’s
burners need cleaning.
1. Turn off the electrical power and close the main manual gas
shutoff valve. See L&O instructions on pages 43 and 44.
Allow boiler parts to cool before disassembly.
2. Remove main burner manifold assembly from boiler.
Refer to parts list supplied with this manual for
disassembly aid.
3. Remove any loose foreign material such as dust or lint with
a vacuum. Check all ports, orices, and air openings for
blockage. Dislodge any foreign material causing blockage.
Remove any soot or carbon deposits with a rag making sure
to remove any lint left on burner by vacuuming again.
OPERATION AND START-UP INSTRUCTIONS