Aarrow Fires Gas Stove Stove User Manual


 
CONNECTING THE GAS SUPPLY
Once the stove is in place it is then possible to
connect the gas supply. The gas supply point is
located centrally at the rear (as show in fig.7) and
should be connected in accordance with the follow-
ing requirements.
Fig. 7
Check that the appliance is suitable for the gas
supply; refer to data labels on packaging and/or the
stove data label for the gas type.
The gas installation must be in accordance with the
current issue of BS6891.Gas supply pressure at the
fire should be 20mbar for natural gas & 37mbar
for LPG.
The gas supply should be connected with the 12mm
fitting and olive supplied with the stove.
A maximum pipe run of 1.5 meters (or 5 feet)
should be adhered to. Copper tubing may be used
provided a distance of 25mm is maintained
between pipe-work and any surface of the stove.
The gas service tap (supplied) should be fitted adja-
cent to the fireplace to enable safe removal of the
appliance for servicing. After fitting the supply,
operate the gas tap (supplied) and check all joints
up to the termination of the supply pipe for gas
tightness using a soap/water solution and the pres-
sure drop method.
To check the pressure to the burner. This must be
carried out with all other gas appliances operating
at maximum. To check the pressure to the burner it
is necessary to ignite the appliance and set to 'high
rate'. (See pressure test sequence).
Fig. 8
PRESSURE TEST SEQUENCE
Controls are located at the base of the stove below
the ash lip.
Ensure supply is isolated and the valve is in
the off position
Step 1. Remove the valve control cover by
unscrewing the pozi screw located by knob B and
lever the retaining tab to the side of knob A.
Step 2. Locate the outlet pressure tap and unscrew
approximately half a turn anti-clockwise with a
small flat bladed screw driver. Connect a pressure
guage to the outlet pressure tap.
Step 3. Re-connect the supply and light stove. (see
lighting and controlling the stove section in the
users instructions section of this manual). Turn to
high setting. Read pressure guage, setting to be -
20 mbar for Natural Gas or
37 mbar for LPG
Step 4. If any adjustment is required, use the brass
screw located between knob B and knob A on the
front of the valve, and adjust accordingly to the
indication symbol marked upon the valve body.
Step 5. Turn off stove and isolate the supply.
Step 6. Disconnect manometer and re-tighten the
outlet pressure tap screw. Do not over tighten.
Step 7 Replace the valve control cover.
Aarrow Sherborne GSL CF 13
INSTALLATION INSTRUCTIONS
Gas Inlet
Rear Of
Valve