Wiring Specification:
Junction Box to 300V, 221°F [105°C]
Electronic Module: 18-24 AWG or larger shielded
PVC, 14 or 26 conductor
Electronic Module 300V, 221°F [105°C]
To Remote Display: 16-20 AWG or larger
PVC 28 conductor
Dimensions/Weights: Electronic Module
(Up to 12 Probe System) 16” [40.6 cm] H x
16” [40.6 cm] W x
8” [20.3 cm] D
Single Transformer 20 lbs [ 9 kg]
Dual Transformer 22 lbs [10 kg]
Manufacturing Standards:
Column: ASME Section 1, ASME B31.1
Electronics: CSA 22.2
NFPA - 70 (NEC)
89/336/EEC
73/23/EEC
Standard Options:
Door Mounted Local Display
Additional Remote Displays: Slaved or
Independently Powered
Note: Displays are available in two sizes, standard and mini.
Displays may be ordered in an enclosure or for panel mounting.
Dual Transformer using two separate mains input
Open/Short Detection
Metallic enclosure for EMI/RFI control – Stainless Steel or Carbon Steel
Keyed Lock-Out Switches
< 1μS sensitivity
Cascaded units to n channels
Specify: Series or Interleaved Probe connections
Shorted probe detection level set to user specified conductivity trip point
(±5% with hysteresis) to indicate change in water chemistry.
4-20 mA instrumentation loop output, galvanic isolation, with geometrically
proportional driven integrative state change