Tyco 12B Water System User Manual


 
15
(4) Restore power to the unit.
If the continuity monitoring option was ordered, the shorted wire detection is
factory set to indicate fault condition upon the detection of the equivalent of
1000 μS water. If the water conductivity sense resistors are changed, the three
short-circuit resistors should be changed at the same time. Refer to figure 6,
location 7 and use the procedure outlined above.
6.0 Spare Parts
The following spare parts are recommended as a minimum set for stocking by the
user:
Probes:
12 point Single Module – stock 2
24 point Two Module – stock 4
36 point or more Systems – stock 6
1 Relay (requires pcb through hole soldering to replace)
A copy of this I.O.M.
Probes are available only as complete new assemblies.
Consult your Tyco or Penberthy distributor or TV&C-Prophetstown
for repair Modules.
7.0 Model 12B Specifications *
Standard Sensitivity:
1μSiemens (10 – 100 μS default)
Input Voltage: 105-130 Vac or optional
210-260 Vac – MOV protected
Frequency: 50-60 Hz
Power (max): depends on system configuration
80 VA dual transformer system
40 VA single transformer system
Output Voltage:
Probes: 12 Vac RMS maximum, resistor isolated
Relay Contact: 8 AMP 28 VDC
10 AMP @ 125 Vac (resistive)
UL & CSA: 10 AMP @ 250 Vac (resistive)
TÜV: 5 AMP @ 250 Vac (resistive)
Operating Temperature:
Electronics: 32 – 160°F [0°C –70°C]
FOR USE IN 121°F [50°C] MAXIMUM AMBIENT (without local display)
FOR USE IN 104°F [40°C] MAXIMUM AMBIENT (with local display)
Standard Column: 850°F [455°C] maximum
Standard Enclosure Rating: NEMA 4X [IP66]