Figure 44. Dimensions and clearances for metal-enclosure EX2
Storage environment
The storage environment must meet the following requirements:
Temperature: From –40°F to 185°F (–40°C to 85°C)
Relative humidity: 5–93%, non-condensing
Mounting location
Trane recommends locating the EX2 module:
In an environment protected from the elements
Where public access is restricted to minimize the possibility of tam-
pering or vandalism
Near the controlled equipment to reduce wiring costs
Where it is easily accessible for service personnel
In conduit, in the same room, and no more than 20 ft (6.1 m) from the
FACP
1 in.
(25 mm)
1 in.
(25 mm)
2 in.
(51 mm)
2 in.
(51 mm)
9 in.
(229 mm)
10.37 in.
(263 mm)
width with
cover
2.25 in.
(58 mm)
1 in.
(25 mm)
6.5 in.
(165 mm)
10.25 in.
(260 mm)
width without cover
7 in.
(178 mm)
9 in.
(229 mm)
Clearances
Dimensions
24 in.
(610 mm)
1.875 in.
(48 mm)
0.28 in.
(7 mm)