Chapter 3
Installation diagrams
Smoke control system overview
An engineered smoke control system can be added on to a Tracer
Summit
building automation system. The system layout, wiring
requirements, and capacities for smoke control applications differ from
Tracer Summit systems that do not employ smoke control.
A smoke control installation includes a Trane building control unit
(BCU), the Tracer MP581 programmable controller, and wiring. These
devices should be wired on the smoke control communication link.
Devices that are a part of the Tracer Summit system, but are not used by
the smoke control system, must be on a separate communication link.
IMPORTANT
For dedicated smoke control system, only Tracer MP581s used for
smoke control are allowed on the LonTalk communication link. Tracer
MP581s and other LonTalk UCMs not involved in smoke control must
be connected to other BCUs. A nondedicated smoke control system can
have other LonTalk devices connected to the communication link.
Installation diagrams consist of system riser and system termination
diagrams. These diagrams provide requirements and restrictions to the
installer.