Trane BAS-APG001-EN Smoke Alarm User Manual


 
Chapter 2 Pre-installation considerations
28 BAS-APG001-EN
Table 5. Sample automatic smoke control matrix (dedicated)
Table 6. Sample automatic smoke control matrix (nondedicated)
Equipment
First smoke zone in alarm
Zone 1 Zone 2 Zone 3 Zone 4
Main sup fan On On On On
Main R/E fan On On On On
Stair press fan On On On On
1st flr sup dmpr Close Open Close Close
1st flr ret dmpr Open Close Close Close
2nd flr sup dmpr Open Close Open Close
2nd flr ret dmpr Close Open Close Close
3rd flr sup dmpr Close Open Close Open
3rd flr ret dmpr Close Close Open Close
4th flr sup dmpr Close Close Open Close
4th flr ret dmpr Close Close Close Open
Smoke zone 1 Alarm Adjacent Unaffected Unaffected
Smoke zone 2 Adjacent Alarm Adjacent Unaffected
Smoke zone 3 Unaffected Adjacent Alarm Adjacent
Smoke zone 4 Unaffected Unaffected Adjacent Alarm
Equipment
First smoke zone in alarm
Zone 1 Zone 2 Zone 3 Zone 4
Main sup fan On On On On
Main R/E fan On On On On
Stair press fan On On On On
1st flr sup dmpr Open Open Open Open
1st flr ret dmpr Open Open Open Open
2nd flr sup dmpr Open Open Open Open
2nd flr ret dmpr Open Open Open Open
3rd flr sup dmpr Open Open Open Open
3rd flr ret dmpr Open Open Open Open
4th flr sup dmpr Open Open Open Open
4th flr ret dmpr Open Open Open Open
Smoke zone 1 Alarm Adjacent Open Open
Smoke zone 2 Adjacent Alarm Adjacent Open
Smoke zone 3 Open Adjacent Alarm Adjacent
Smoke zone 4 Open Open Adjacent Alarm