Trane BAS-APG001-EN Smoke Alarm User Manual


 
Methods of smoke control
BAS-APG001-EN 3
Figure 1: Sample pressure difference across a barrier
Table 1 provides the National Fire Protection Association (NFPA)
recommended minimum pressure difference between the high-pressure
side and the low-pressure side.
Table 1: Recommended minimum pressure difference
Table 2 on page 4 provides the NFPA recommended maximum allowable
pressure difference across doors. The listed pressure differences take into
account the door closer force and door width.
Building type
Ceiling height
(ft [m])
Minimum pressure
difference
(In.w.c. [Pa])
Sprinklered Any 0.05 (12.4)
Non-sprinklered 9 (2.7) 0.10 (24.9)
Non-sprinklered 15 (4.6) 0.14 (34.8)
Non-sprinklered 21 (6.4) 0.18 (44.8)
Notes:
The minimum pressure difference column provides the pressure
difference between the high pressure side and the low-pressure side.
The minimum pressure difference values incorporate the pressure
induced by the buoyancy of hot smoke.
A smoke control system should maintain the minimum pressure
differences regardless of stack effect and wind.
The minimum pressure difference values are based on
recommendations in NFPA 92A (NFPA 2000, Recommended Practice
for Smoke Control Systems).
In.w.c. is inches of water column.
Pa is Pascals.