Trane BAS-APG001-EN Smoke Alarm User Manual


 
Chapter 8 Network variable bindings
128 BAS-APG001-EN
UUKL binding list (actuator Open/Close or
On/Off status)
Table 34 shows an example list of actuator status custom bindings.
Actuator Open/Close or On/Off status is sent from the mechanical system
directly to the FSCP.
Table 34. Actuator status custom bindings
Function Originator Network variable Destination
supplyFanStatus Mechanical system nvoSwitch01 MP580-3/nviSwitch04
returnFanStatus Mechanical system nvoSwitch02 MP580-4/nviSwitch03
stairFanStatus Mechanical system nvoPercent01 MP580-2/nviPercent02
oaDamperStatus Mechanical system nvoPercent04 MP580-3/nviPercent01
raDamperStatus Mechanical system nvoPercent05 MP580-2/nviPercent01
eaDamperStatus Mechanical system nvoPercent06 MP580-4/nviPercent01
supplyDamperFloor01 Mechanical system nvoPercent07 MP580-3/nviPercent02
returnDamperFloor01 Mechanical system nvoPercent08 MP580-3/nviPercent03
supplyDamperFloor02 Mechanical system nvoPercent09 MP580-3/nviPercent04
returnDamperFloor02 Mechanical system nvoPercent10 MP580-3/nviPercent05
supplyDamperFloor03 Mechanical system nvoPercent11 MP580-4/nviPercent02
returnDamperFloor03 Mechanical system nvoPercent12 MP580-4/nviPercent03
supplyDamperFloor04 Mechanical system nvoPercent13 MP580-4/nviPercent04
returnDamperFloor04 Mechanical system nvoPercent14 MP580-4/nviPercent05