Trane BAS-APG001-EN Smoke Alarm User Manual


 
Chapter 8 Network variable bindings
126 BAS-APG001-EN
UUKL binding list (smoke alarm status)
Table 32 shows an example list of smoke alarm custom bindings. In order
to comply with UL-864 annunciation and control requirements, smoke
alarm signals are sent to the mechanical system, FSCP lamps, and audio
alarms (Sonalerts). Smoke alarms specific to a zone are broadcast to
annunciate smoke alarms regardless of control sequence. A general
smoke alarm is broadcast to signal a switch from HVAC control mode to a
smoke control mode. Floor alarms are sent as an analog value to comply
with the subsequent alarms requirement.
Table 32. Smoke alarm custom bindings
Function Originator Network variable Destination
Smoke alarm any MP580-2 nvoSwitch02 Mechanical system /nviSwitch37
nvoSwitch02 MP580-3/nviSwitch37
nvoSwitch02 MP580-4/nviSwitch37
smokeAlarmFloor01 MP580-2 nvoSwitch05 Mechanical system /nviSwitch20
nvoSwitch05 MP580-3/nviSwitch09
smokeAlarmFloor02 MP580-2 nvoSwitch06 Mechanical system/nviSwitch21
nvoSwitch06 MP580-3/nviSwitch12
smokeAlarmFloor03 MP580-2 nvoSwitch07 Mechanical system/nviSwitch22
nvoSwitch07 MP580-4/nviSwitch08
smokeAlarmFloor04 MP580-2 nvoSwitch08 Mechanical system/nviSwitch23
nvoSwitch08 MP580-4/nviSwitch11
supplyDuctSmokeDetect MP580-2 nvoSwitch09 Mechanical system/nviSwitch30
nvoSwitch09 MP580-3/nviSwitch06
returnDuctSmokeDetect MP580-2 nvoSwitch10 Mechanical system/nviSwitch31
nvoSwitch10 MP580-4/nviSwitch05
stairDuctSmokeDetect MP580-2 nvoSwitch11 Mechanical system/nviSwitch32
nvoSwitch11 MP580-4/nviSwitch01
stairShaftSmokeDetect MP580-2 nvoSwitch12 Mechanical system/nviSwitch33
smokeFloorAlarm MP580-2 nvoPercent20 Mechanical system/nviPercent20
nvoPercent20 MP580-3/nviPercent20
nvoPercent20 MP580-4/nviPercent20