Sentry Industries 5000 Carbon Monoxide Alarm User Manual


 
SMC sierra monitor corporation Sentry Instruction Manual - Version 6
APPENDIX A - SPECIFICATIONS
Page: 85
8.1 APPENDIX A - SPECIFICATIONS
A. OPERATING
OPERATING TEMPERATURE
Controller 32 to 122
o
F (0 to 50
o
C)
STORAGE TEMPERATURE
Controller: -40 to 130
o
F (-40 to 55
o
C)
HUMIDITY
Controller: 10% to 95% RH
POWER
Standard 120 VAC +10%/-15%, 60 Hz
12 VDC Nom; 10 to 29 VDC
Optional 220 VAC +10%/-15%, 50 Hz
12 VDC Nom; 10 to 29 VDC
Consumption 48 Watts max. (eight modules)
RELAYS
Three DPDT 3A, 115 VAC (Low, High, Trouble)
Sixteen SPDT 6A, 115 VAC (Model 5392-00)
Sixteen SPDT 6A, 115 VAC (Model 4314-01)
ANALOG OUTPUTS
Eight 4-20 mA, channel value (Model 4314-01)
Loop Resistance max. 800 Ohms
NUMBER OF CHANNELS
5000-02: Two channels, upgradeable to four or eight
5000-04: Four channels, upgradeable to eight
5000-08: Eight channels
PRINTER INTERFACE
Standard on 5000-08, option on -02 & -04
RS232 Port 1200 Baud
8 bits, no parity
1 start bit, 2 stop bits
MODBUS INTERFACE (Replaces printer interface)
Optional MODBUS communication protocol
Honeywell Multivendor Approved for TDC 3000 Gateway
COMPONENTS
Microprocessor Z84 (4 MHz - 8 bit CPU)
Memory 64K bytes EPROM
8K bytes Static RAM
(battery backed-up)
Displays 4 digit 1/2” LCD
32 character (2X16) dot matrix
alphanumeric LCD
11 LED indicators
Battery Hi energy lithium
3 year retention
Keypad 7 key sealed membrane
Power Supply Integral High efficiency AC/DC with
line filter
TRANSMISSION
Digital, pulse width modulated - RFI, EMI immune
B. PHYSICAL
DIMENSIONS
Controller
Rack Mount 7" X 4.5" X 12" (H W D)
17.5cm X 11.25cm X 30cm
NEMA 4X Enclosure 17.5" X 16.2" X 6.35" (H W D)
44.5cm X 41.1cm X 16cm
NEMA 7 Enclosure 22.0" X 21.5" X 14" (H W D)
55.9cm X 54.6cm X 35.6cm
Module Housing
Environment NEMA 7 (NEMA 4X Optional)
5100-01, 5100-02 7.5" X 4" X 4" (H W D)
19cm X 10cm X 10cm
5100-03 8.5" X 4" X 4" (H W D)
19cm X 10cm X 10cm
5100-04 : -24, -27 7.5" X 4" X 4" (H W D)
19cm X 10cm X 10cm
5100-25 10" X 4" X 4" (H W D)
19cm X 10cm X 10cm
WEIGHT
Controller
Rack Mount 7 pounds (3.2 kg)
NEMA 4X Enclosure 25 pounds (11.3 kg)
NEMA 7 Enclosure 143 pounds (65.0 kg)
Module
2 pounds (0.9 kg)
MOUNTING
Controller Instrument Rack
Chassis Mount Panel
Wall Mount Bracket
NEMA 4X Enclosure
NEMA 7 Enclosure
Module Conduit or flexible cable
MODULE CABLE
Typical: three conductor 18 AWG,
See installation instructions for alternative wire sizes
SENSOR TYPES
Hydrogen Sulfide Thin film, solid state (5100-01)
Combustible Catalytically bead (5100-02)
Oxygen Electrochemical (5100-03).
Carbon Monoxide (CO)
Electrochemical (5100-04)
Hydrogen Sulfide Electrochemical (5100-05)
Chlorine Electrochemical (5100-06)
Hydrogen Electrochemical (5100-07)
Sulfur Dioxide Electrochemical (5100-10)
Nitrogen Dioxide Electrochemical (5100-12)
CO High Range Electrochemical (5100-13)
CO - Hydrogen Tolerant Electrochemical (5100-16)
Nitric Oxide electrochemical (5100-19)
Hydrogen Chloride Electrochemical (5100-21)
Hydrogen Cyanide Electrochemical (5100-22)
Ammonia Electrochemical.(5100-25)
Ethylene Oxide Electrochemical (5100-27)