APPENDIX G - MODEL 4314 OUTPUT EXPANSION PANEL
Page: 104
8.7.5 OUTPUT EXPANSION PANEL TESTING
The relay outputs can be forced to the energized state by
using the front panel TEST ALARMS function.
The analog outputs can be forced to 4 mA by using
diagnostic code 0012.
The analog outputs can be forced to 20 mA by using
diagnostic code 0013.
The analog outputs can be returned to normal operation
by using diagnostic code 0000.
8.7.6 INDIVIDUAL RELAY SPECIFICATIONS
Dimensions 7.0” X 4.2” X 1.2” (HWD)
Relays
Number of Relays 16 SPDT
Contact Rating 6A
Wire Terminals Screw Terminals
Analog Outputs
Number of Outputs 8
Scale 4-20 mA
Loop Resistance (max.) 800 Ohms
Wire Terminals Compression