SMC sierra monitor corporation Sentry Instruction Manual - Version 6
SERVICE
Page: 65
7.3.6 DIAGNOSTIC REPORT
A Diagnostic report can be printed using diagnostic codes
0008 or 0010. Figure 7-4 is a typical report..
ID:A 11/20 15:16
S1= +0.376 BV= +2.021 BI= 0.323 SP= 0653
ST= +0.284 MV= +19.0 CS= +0.000
S2= +1.20 HV= +0.920 HI= +0.975 SP= 400
ST= +0.009 MV= +19.4 CS= +0.000
Figure 7-4
Typical Diagnostic Report
Table 7-2 is a description of the information contained in
a typical diagnostic report
Report Description
ID:A Controller Identification
11/20 15:16 Time report was generated
S1 +0.376 Data that follows is for Module 1
Sensor Signal is +0.376 VDC
BV +2.021 Bridge Voltage 2.021 VDC
BI +0.322 Bridge Current 323 mA
SP 0653 Sensor Power 653 mW
ST +0.284 Sensor Type
(Where: .2 -.3 VDC: Combustible)
MV +19.0 Module Voltage = 19 VDC
CS +0.000 Calibration Switch
Off 0.000, On = 2.5 VDC
S2 +1.20 Data that follows is for Module
Sensor Signal is + 1.20 VDC
HV +0.920 Heater Voltage Signal
HI +0.975 Heater Current Signal
SP 400 Sensor Power 400 mW
ST +0.009 Module Type
(Where: .11-.1 VDC: H2S)
Table 7-2
Diagnostic Report Description