Sapphire Audio DV425TR Electric Heater User Manual


 
DV425TR DIRECT VENT ROOM HEATER
02/01 Page 29 250-5533
NOTE:
(1) Installation requires a minimum of 1’ (305mm) horizontal run of vent with a ” (6mm) rise run towards the
termination. Each 1’ (305mm) of horizontal venting must include a 1/4” rise. Never allow the vent to run
downward. This could cause high temperatures and may present the possibility of a fire.
(2) The location of the horizontal vent termination on an exterior wall must meet all local and national building
codes, and must not be easily blocked or obstructed, see page 26.
(3) For installations requiring a vertical rise on the exterior of the building, Aladdin Snorkle Kit #844-8920, 14”
(356mm) and 36” (914mm) tall snorkel terminations are available. Follow the same installation procedures
as used for standard horizontal terminations. If the snorkel termination must be installed below grade
(i.e. basement application), proper drainage must be provided to prevent water from entering the snorkel
termination. Do not backfill around snorkel termination.
Step 3.
With the adapter and pipe attached to the stove, slide the stove into its correct location, maintaining
minimum clearance to combustibles. Mark the wall for a 10” x 10” (254mm x 254mm) square hole. The center
of the square hole should line up with the centerline of the horizontal pipe, as shown in Fig. 6. Cut and frame
the hole in the exterior wall where the vent will be terminated. If the wall being penetrated is constructed of
noncombustible material, i.e. masonry block or concrete, a 7” (178mm) diameter hole is acceptable.
Also, if you have installed the Hearth Legs, they will reduce the centerline clearance by 3"
(75mm).
HORIZONTAL INSTALLATION, cont.
FIG. 6
CENTER
LINE
CENTER
LINE
CENTER OF
HOLE
WALL
THIMBLE
FIG. 6-A
CENTER
LINE
WALL
THIMBLE
CENTER
LINE
CENTER OF
HOLE