Regency FP90 Indoor Fireplace User Manual


 
FPI FP90 Wood Fireplace8
INSTALLATION
No Combustibles on Face of Unit.
Combustibles May Not Extend to
Unit Face.
Do not notch wallboard around
standoffs.
INSTALLATION
The FP90 may be placed on or near construction
materials. The combustion air kit, re stop spacer
and roof ashings (not chase ashings) may be
placed directly on or against normal construction
materials. The chimney requires a minimum 2"
(51mm) clearance. A combustible mantle (to a
depth of 10", 254mm) may be installed no closer
than 18" (457mm) above the warm air vent or
55-1/2" (1410mm) from bottom of unit.
The chimney must be enclosed when installed
in or passing through a living area where
combustible material or people may come in
contact with it. This is important to prevent
possible personal injury or re hazard.
For any further information, please call your
dealer. Special restrictions apply to the front and
facing of the replace and nearby walls.
WARNING: If insulation is used, do not place
the unit against it. Insulation or vapor barriers,
if used, must be secured to assure insulation
and vapor barriers remain in place and do not
affect the required air spaces.
WARNING: Do not pack or ll required air spaces
with insulation or other material. No material of
any kind is allowed in these areas.
NOTES:
1) Do not insulate the chase cavity with blown
or ll type insulation materials.
2) Local codes may not require restopping
at the ceiling level for outside chase
installations; however, it is recommended
for safety and the reduction of heat loss.
3) We recommend that you insulate at least
the rst oor of the chase to prevent heat
loss.
4) Some local codes require 1 hour re rating
on one or all sides of re chases. Check
with your local authorities.
CLEARANCES AND HEIGHT REQUIREMENTS
Clearances to Combustibles
Max. 10" (254mm)
Depth of Mantel
center line 18" (457mm)
55-1/2" (1410mm)
from bottom of unit
2"
(51mm)
Mantel leg can
go in this
area
5"
(127mm)
40" (1016mm)
20" (508mm)
18" (457mm)
NOTE FOR MANTEL LEGS:
For every 1" (25mm) pretrusion
greater than 5" (127mm), you
must travel away from the unit
1" (25mm) starting at 2" (51mm)
from the edge of the hearth
extension.