VOYAGEUR Wood Insert
R
F. Prefabricated Metal Chimney
E. Metal Heat Circulating Masonry
The chimney can be new or existing, masonry or prefabricated
and must meet the following minimum requirements:
• Must be minimum 6 inch (152mm) inside diameter of
high temperature chimney listed to UL 103 HT (2100
o
F)
or ULC S628.
• Must use components required by the manufacturer for
installation.
• Must maintain clearances required by the manufacturer
for installation.
• Refer to manufacturers instructions for installation
•This insert is listed to UL 1482 Standard and is
approved for installation into listed factory-built solid
fuel
fi replaces listed to UL 127 conforming to the follow-
ing specifi cations and instructions:
•The original factory-built clearance fi replace chimney
cap must be re-installed after installing the approved
chimney liner meeting type UL 103 HT requirements
(2100°F) per UL 1777.
•The liner must be securely attached to the insert fl ue
collar and the chimney top.
•The air fl ow of the factory-built solid fuel fi replace
system must not be altered. The fl ue liner top support
attachment must not reduce the air fl ow for the existing
air-cooled chimney system.
•No dilution air is allowed to enter the chimney.
1. Secure the fi replace damper in the open position.
If this cannot be accomplished, it will be necessary
to remove the damper.
2. Seal damper area of chimney around chimney
connector with a high temperature sealant or seal
insert against the face of the fi replace.
3. Both methods must be removable and replaceable
for cleaning and re-installation.
This insert conforms with the safety standard UL-1482 and
ULC S628 (Canada) in all respects and is approved to UL &
ULC safety standards for installation and use within a fi re-
place with masonry chimney, in accordance with NFPA 211,
and CAN/CSA-B365-01.
Minimum Width of Cavity Opening - Front
32-7/8* 835
Minimum Width of Cavity Opening - Rear
19-1/8* 486
Minimum Height
21-1/2* 546
Minimum Depth from Front to Rear
18-1/8* 460
Inches Millimeters
Fire Risk.
When lining air-cooled factory-built chimneys:.
• Run chimney liner approved to UL 1777 Type
HT requirements (2100 degrees F)
• Re-install original factory built chimney cap
ONLY
• DO NOT block cooling air openings in chimney
• Blocking cooling air will overheat the chimney
WARNING
NOTICE: In Canada when using a factory-built chimney it must
be safety listed, Type UL103 HT (2100
o
F) [1149
o
C] CLASS
“A” or conforming to CAN/ULC-S629M, STANDARD FOR
650
o
C FACTORY-BUILT CHIMNEYS.
NOTE: Refer to chimney liner manufacturer for recom-
mendations on supporting the liner. Installation into
fi replaces without a permit will void the listing.
WARNING! Risk of Fire!
Follow venting manufacturer’s clearances and
instructions when installing venting system.
To maintain the functionality of the fi replace’s chimney
system you may use a Simpson Dura-Vent DuraLiner
Slip Hanger, Part # 4671, and attach to the bottom of the
fi replace chimney cap to support the liner. You have two
options to completing the installation.
Option one - Not required to use liner cap:
Re-attach the existing top of the chimney cap.
Option two - Using liner cap:
Re-attach the existing top of the chimney cap and install a
new storm collar and a new liner cap.
*You will need to add additional clearances to these
dimensions for your specifi c installation. Also allow suf-
fi cient clearance if you are installing an outside air kit.