Baxi Potterton 30 HE Fan User Manual


 
50
© Baxi Heating UK Ltd 2007
16.0 Fault Finding
Fault Finding Solutions Sections A to E
Is there 230V at:
Is there 230V at:
Main terminals L and N Check electrical supply
1.
NO
Main terminal fuse
Replace fuse
Replace PCB
neon
illuminated
2.
YES
Selector terminals a & b and a
& 3. PCB - A4 connector
terminals 4 & 5
Check wiring
Replace selector
3.
NO
NO
A
Pump Replace pump
1.
NO
PCB - A4 connector terminals 3 & 6
Replace PCB
2.
NO
Change pump supply cable
YES
B
CH system pressure 0.5 to 1.5 bar Re-pressurise system
1.
NO
Primary flow valve diaphragm damaged Replace diaphragm
Flow valve rod obstructed
3.
YES
Check the tap of the automatic air
vent is opened
Open the automatic air vent
2.
NO
NO
C
YES
Continuity across flow
microswitch and PCB - A5
connector terminals 7 & 8
Replace microswitch
1.
NO
NO
Primary temperature sensor faulty.
Cold resistance approx. 11K ohms
(resistance reduces with increase in temp.)
Replace sensor
2.
YES
Fan connections correct at fan.
PCB - A2 connector, is 230V
across terminals 5 & 7
Fan jammed or faulty winding
Replace PCB
Replace fan
YES
3.
D
If pump jammed, release