For blower units with enclosure and filter, add
the following static pressures to the static
pressure determined by the system designer
for total external static pressure.
19
PERFORMANCE DATA - CONTINUED
BAE50
0.1" W.C.
BAE75
0.2" W.C.
BAE100
0.1" W.C.
BAE125
0.1" W.C.
BAE145
0.2" W.C.
BAE175
0.1" W.C.
BAE200
0.1" W.C.
BAE225
0.1" W.C.
BAE250
0.2" W.C.
BAE300
0.2" W.C.
BAE350
0.2" W.C.
B
AE400
0.2" W.C.
Models With or Without Blower Enclosure
➀ ➁ ➂ ➃ ➄
F
ilters
0.5 Static Air Pressure 0.6 Static Air Pressure
Temp Sheave Sheave
Model Rise Airflow RPM HP Drive Turns RPM HP Drive Turns
No. (°F) (cfm) No. Open No. Open
40 938 – – – – – – – –
45 833 940 3.5 – – – –
50 750 920 4 – – – –
B
AE
55 682 905 4 – – – –
5
0
60 625 895 4 – – – –
65 577 890 4 – – – –
70 536 890 4 – – – –
40 1406 925 4 985 3/4 C91 3
45 1250 890 4 955 3.5
50 1125 865 4.5 930 3.5
B
AE
55 1023 845 4.5 910 4
7
5
60 938 830 5 895 4
65 865 820 0 885 4
70 804 810 0.5 875 1/3 C114 4.5
40 1875 625 2 – – – –
45 1667 610 2 – – – –
50 1500 595 2.5 – – – –
B
AE
55 1364 585 2.5 – – – –
1
00
60 1250 580 3 – – – –
65 1154 570 3 – – – –
70 1071 570 3 – – – –
40 2315 665 3/4 C38 3 – – – –
45 2058 640 3.5 – – – –
50 1852 625 3.5 – – – –
B
AE
55 1684 610 4 – – – –
1
25
60 1543 600 4 – – – –
65 1425 590 4 – – – –
70 1323 585 4.5 – – – –
40 2685 845 1 1/2 C113 2.5 885 1 1/2 C113 1.5
45 2387 795 1 C38 0.5 835 1 C38 0
50 2148 760 1.5 800 0.5
B
AE
55 1953 730 2 775 1
1
45
60 1790 710 2 755 1.5
65 1652 690 2.5 740 1.5
70 1534 680 2.5 730 2
40 3281 620 1 C107 3.5 – – – –
45 2917 590 4.5 – – – –
50 2625 565 4.5 – – – –
B
AE
55 2386 545 3/4 C101 0.5 – – – –
1
75
60 2188 530 0.5 – – – –
65 2019 520 1 – – – –
70 1875 510 1 – – – –
40 3704 665 1 1/2 C105 3 – – – –
45 3292 625 0 – – – –
50 2693 595 0.5 – – – –
B
AE
55 2694 570 1.5 – – – –
2
00
60 2469 555 1.5 – – – –
65 2279 540 2 – – – –
70 2116 530 2.5 – – – –
40 4219 805 2 C108 1 – – – –
45 3750 745 2.5 – – – –
50 3375 700 3.5 – – – –
B
AE
55 3068 670 1 C107 3 – – – –
2
25
60 2813 640 3.5 – – – –
65 2596 620 3.5 – – – –
70 2411 600 4 – – – –
40 4630 855 3 C111 2 880 3 C111 1.5
45 4115 790 2 C33 3.5 820 2 C33 3
50 3704 740 0.5 770 1 1/2 C100 4
B
AE
55 3367 705 1.5 735 1 1/2 C105 0.5
2
50
60 3086 670 1 C109 5 705 4.5
65 2849 645 3/4 C109 5 680 4.5
70 2646 625 3/4 C16 0 660 3/4 C109 5
40 5556 – – – – – – – –
45 4938 865 3 C111 2 890 1.5
50 4444 805 3.5 830 2.5
B
AE
55 4040 755 4.5 780 2 C33 4
3
00
60 3704 715 1.5 745 0.5
65 3419 685 2 715 1.5
70 3175 660 1 C109 5 690 2
40 6481 – – – – – – – –
45 5761 985 5 C116 2 1005 1.5
50 5185 910 3.5 935 3
B
AE
55 4714 850 5 875 3 C116 4
3
50
60 4321 800 1 830 0.5
65 3989 760 2 790 1.5
70 3704 730 1 1/2 C106 3 755 1 1/2 C106 2.5
40 7407 – – – – – – – –
45 6584 965 2.5 990 2
50 5926 895 4 925 3
B
AE
55 5387 840 0 870 3 C116 4.5
4
00
60 4938 795 1 825 0.5
65 4558 760 2 795 1
70 4233 730 3 765 2 C108 2
➀
Shaded area indicates the unit’s standard motor &
standard drive arrangement. For operation outside the
shaded area, specify motor Hp and drive number.
➁
Outputs shown are for elevations up to 2000'. For ele-
vations over 2000’, output needs to be reduced 4% for
each 1000' above sea level. (Does not apply in
Canada - see rating plate)
➂
Sheave turns open are approximate. For proper opera-
tion, check blower rpm.
➃
Mounting height and throw for BV models (w/o duct-
work or nozzles and at Cfm’s yielding a 55° tempera-
ture rise), are the same as those listed on page 8 for
equivalent PV models.
➄
Rpm setting shown in
bold
type indicate factory set-
tings and standard drives.
1/3
1/4
1/2
1/3
1/3
1/4
1/3
1/3
1/2
1/2
1/2
1 1/2
3/4
2
2
3
5
1 1/2
1
3/4
3/4
1/2
C1
C91
C114
C90
C95
1/2
C96
C95
C37
C38
C38
C38
C101
C16
C16
1 1/2
C106
C16
C105
C105
C33
C108
C118
C116
C107
3/4
C107
1/2
1/2
1
3
1 1/2
5
3
3/4
C1
C91
C38
C38
C109
C111
C105
C116
C118
Data for use with filters only
3
C116
2
C108
2
C108
5 C116
Heater Parts from ACF Greenhouses