Modine Manufacturing PAE Gas Heater User Manual


 
Model PAE 50 PAE 75 PAE 100 PAE 125 PAE 145 PAE 175 PAE 200 PAE 225 PAE 250 PAE 300 PAE 350 PAE 400
S S S S S S S S S S S S
8'
14 23 23 34 46 32 44 44 65 57 68 74
10'
12 21 20 30 42 29 39 39 58 51 60 66
12'
11 19 19 27 38 26 36 36 53 47 55 60
14'
17 17 25 35 25 33 33 50 43 51 56
16'
16 16 23 33 23 31 31 46 41 48 52
18'
22 31 22 29 29 44 38 45 49
20'
21 29 21 28 28 41 36 43 47
22'
27 26 40 35 41 45
24'
25 25 38 33 39 43
26'
36 32 38 41
28'
35 31 36 40
30'
34 30 35 38
32'
34 37
3
4'
36
16
PERFORMANCE DATA – HOODS
Performance Data — 30°, 60° and 90° Downward Deflector Hoods — Propeller Models
MOUNTING
HEIGHT
X
Y
Y
Z
Z
X
60° NOZZLE
30° NOZZLE
60°
30°
30° DOWNTURN NOZZLE
60° DOWNTURN NOZZLE
NOTE:
X = FEED FROM HEATER
TO START OF
FLOOR COVERAGE.
Y = FEET TO END OF
FLOOR COVERAGE.
Z = FEET TO END OF
THROW.
30° HOOD 60° HOOD
THROW-FLOOR COVERAGE
Model PAE 50 PAE 75 PAE 100 PAE 125 PAE 145 PAE 175 PAE 200 PAE 225 PAE 250 PAE 300 PAE 350 PAE 400
X Y Z X Y Z X Y Z XY Z X Y Z X Y Z XY Z X Y Z X Y Z X Y Z XY Z X Y Z
8'
6 14 19 10 24 32 9 22 31 14 30 41 18 38 52 13 28 39 17 36 49 17 36 49 23 48 65 20 42 57 23 48 65 24 50 68
10'
9 21 30 8 19 27 12 29 39 17 37 51 11 26 36 15 35 47 15 34 47 22 47 64 19 41 56 22 47 64 23 49 67
12'
6 17 24 5 13 19 11 26 36 16 36 49 10 24 33 14 33 45 14 33 45 21 46 63 18 40 54 21 46 62 22 48 65
14'
9 23 32 14 34 47 7 19 27 13 31 42 12 30 42 20 44 61 16 38 52 20 44 61 21 47 64
16'
12 31 43 10 27 38 10 27 37 18 42 58 15 36 49 18 42 58 19 45 62
18'
7 20 29 7 20 29 17 40 56 13 33 45 16 40 55 18 43 59
20'
15 37 52 10 27 38 15 37 51 16 40 55
22'
12 32 45 12 32 45 14 36 51
2
4'
9 27 39
Mounting
Height to
Bottom of
Heater
30° Downward Hood For Propeller Units
Mounting
Height to
Bottom of
Heater
90° Downward Hood For Propeller Units
Data Based on units fired at full rated input with an entering air temperature of 60°-80°F. Maximum mounting heights higher versus units without outlet devices.
Model PAE 50 PAE 75 PAE 100 PAE 125 PAE 145 PAE 175 PAE 200 PAE 225 PAE 250 PAE 300 PAE 350 PAE 400
X Y Z X Y Z X Y Z X Y Z X Y Z XY Z X Y Z X Y Z X Y Z X Y Z X Y Z X Y Z
8'
0 13 18 0 24 33 0 22 30 0 32 43 0 41 56 0 30 40 0 38 52 0 38 51 0 51 70 0 45 61 0 51 69 0 53 73
10'
0 21 29 0 18 25 0 29 40 0 39 54 0 27 37 0 36 49 0 36 49 0 50 68 0 43 59 0 49 68 0 52 71
12'
0 15 21 0 9 13 0 26 36 0 37 51 0 23 32 0 34 46 0 33 45 0 48 66 0 41 57 0 48 65 0 50 69
14'
0 21 29 0 34 47 0 16 23 0 30 41 0 30 41 0 46 63 0 39 53 0 46 62 0 48 66
16'
0 15 22 0 30 41 0 25 35 0 25 34 0 43 59 0 35 49 0 43 59 0 46 63
18'
0 24 33 0 14 19 0 14 19 0 40 55 0 31 42 0 40 54 0 43 59
20'
0 35 49 0 23 32 0 35 48 0 39 53
22'
0 28 39 0 16 23 0 28 39 0 33 46
2
4'
0 21 30 0 22 31
Mounting
Height to
Bottom of
Heater
60° Downward Hood For Propeller Units
Heater Parts from ACF Greenhouses