Modine Manufacturing PAE Gas Heater User Manual


 
Model BAE 50 BAE 75 BAE 100 BAE 125 BAE 145 BAE 175 BAE 200 BAE 225 BAE 250 BAE 300 BAE 350
BAE 400
X Y Z X Y Z X Y Z X Y Z X Y Z X Y Z X Y Z X Y Z X Y Z X Y Z X Y Z X Y Z
8'
11 24 33 16 35 48 16 35 48 21 44 60 23 46 63 21 43 59 25 50 69 26 53 71 29 58 79 30 61 83 36 71 97 36 71 97
10'
9 22 30 15 34 46 15 34 46 20 43 59 21 46 62 20 42 58 24 50 68 25 52 70 28 57 78 29 60 82 35 71 96 35 70 96
12'
7 18 25 14 32 44 14 32 44 19 42 57 20 44 60 18 41 56 22 49 66 23 51 69 26 56 77 28 59 81 34 70 95 34 70 95
14'
12 29 41 12 29 41 17 40 55 19 43 59 17 39 54 21 47 65 22 49 68 25 55 75 27 58 80 33 69 94 33 69 94
16'
10 26 36 10 26 36 16 38 52 17 41 56 16 37 51 20 45 62 21 48 66 24 54 74 26 57 78 32 68 93 31 68 93
18'
14 35 49 16 38 53 14 34 48 18 43 60 19 46 63 23 52 71 24 56 76 30 67 92 30 67 91
20'
12 31 43 14 35 49 11 30 42 16 41 56 18 43 60 21 50 69 23 54 74 29 65 90 29 65 89
22'
14 37 52 16 40 56 18 48 66 21 51 71 28 64 88 27 63 87
24'
10 29 42 13 35 50 17 44 62 20 49 68 26 62 85 26 61 85
26'
15 40 56 17 45 63 25 59 82 24 59 82
28'
11 32 46 14 39 56 23 57 79 23 56 78
3
0'
21 53 74 20 52 74
17
PERFORMANCE DATA – HOODS
Performance Data — 30°, 60° and 90° Downward Deflector Hoods — Blower Models
H
S
S
90° HOOD
Mounting
Height to
Bottom of
Heater
30° Downward Hood For Blower Units
Model BAE 50 BAE 75 BAE 100 BAE 125 BAE 145 BAE 175 BAE 200 BAE 225 BAE 250 BAE 300 BAE 350
BAE 400
X Y Z X Y Z X Y Z XY Z X Y Z X Y Z X Y Z X Y Z X Y Z X Y Z X Y Z X Y Z
8'
0 25 34 0 37 50 0 37 50 0 47 64 0 49 67 0 46 63 0 54 73 0 56 77 0 62 85 0 65 89 0 77 105 0 76 104
10'
0 22 30 0 35 48 0 35 48 0 45 62 0 48 66 0 45 61 0 53 72 0 55 75 0 61 83 0 64 88 0 76 103 0 75 103
12'
0 16 22 0 32 44 0 32 44 0 43 59 0 46 63 0 43 59 0 51 70 0 53 73 0 59 81 0 63 86 0 75 102 0 74 101
14'
0 29 40 0 29 40 0 41 56 0 44 60 0 40 55 0 49 67 0 52 70 0 58 79 0 61 84 0 73 100 0 73 100
16'
0 23 32 0 23 32 0 38 52 0 41 57 0 37 51 0 47 64 0 49 67 0 56 76 0 60 81 0 72 98 0 71 98
18'
0 34 47 0 38 52 0 33 45 0 43 60 0 46 64 0 53 73 0 57 78 0 70 96 0 70 95
20'
0 28 38 0 33 45 0 26 37 0 40 54 0 43 59 0 50 69 0 55 75 0 68 93 0 67 92
22'
0 24 34 0 34 47 0 38 53 0 47 64 0 51 71 0 65 90 0 65 89
24'
0 25 35 0 31 43 0 42 58 0 47 65 0 63 86 0 62 85
26'
0 36 50 0 42 58 0 59 81 0 59 81
28'
0 23 33 0 34 58 0 55 76 0 55 75
30'
0 50 69 0 49 68
3
2'
0 43 60 0 42 59
Mounting
Height to
Bottom of
Heater
60° Downward Hood For Blower Units
Model BAE 50 BAE 75 BAE 100 BAE 125 BAE 145 BAE 175 BAE 200 BAE 225 BAE 250 BAE 300 BAE 350 BAE 400
S S S S S S S S S S S S
8'
24 38 41 55 60 58 71 75 86 96 121 124
10'
22 34 36 50 54 52 64 67 77 86 109 111
12'
20 31 33 45 49 47 58 61 71 79 99 101
14'
18 29 31 42 45 44 54 57 65 73 92 94
16'
17 27 29 39 42 41 50 53 61 68 86 88
18'
25 27 37 40 39 47 50 58 64 81 83
20'
24 26 35 38 37 45 48 55 61 77 78
22'
23 25 34 36 35 43 46 52 58 73 75
24'
32 35 33 41 44 50 56 70 72
26'
31 33 32 40 42 48 54 68 69
28'
30 32 31 38 40 46 52 65 66
30'
31 30 37 39 45 50 63 64
32'
36 38 43 48 61 62
3
4'
35 37 42 47 59 60
Mounting
Height to
Bottom of
Heater
90° Downward Hood For Blower Units
Data Based on unit fired at full rated input, 60°-80°F entering air temperature, and a 40°F temperature rise through unit.
Maximum mounting heights higher versus units without outlet devises.
Heater Parts from ACF Greenhouses