Mitsubishi Electronics PUHY-P-YMF-B Air Conditioner User Manual


 
27
ENGLISH
Permissible Lengths Prohibited Items
Longest Transmission Cable Length
(1.25 mm
2
)
L1 + L2, L2 + L3, L3 + L1
=
200 m
Remote Controller Cable Length
1 If 0.5 to 0.75 mm
2
r1 , r2
=
10 m
2 If the length exceeds 10 m, the
exceeding section should be 1.25
mm
2
and that section should be a
value within the total extension
length of the transmission cable
and maximum transmission cable
length (L3).
Same as above
Same as above
Use the indoor unit
(IC) address plus 150
as the sub remote
controller address. In
this case, it is 152.
Three or more remote
controllers (RC)
cannot be connected
to one indoor unit.
A Main
B Sub
The remote control-
ler address is the
indoor unit main
address plus 100. In
this case, it is 101.
A Main
B Sub
AB AB
M1
M2 M1 M2 S
OC
(51)
IC
M1 M2
SM1 M2
S
TB5
(01)
IC
TB5
(02)
RC
TB6
(101)
RC
TB6
(151)
RC
TB6
(102)
RC
TB6
(104)
RC
TB6
(103)
TB3 TB7
A
B
M1 M2
A B S
OC
IC
(51)
M1 M2 S
TB5
RC
(01)
IC
M1 M2 S
TB5
(02)
TB6
(102)
TB7TB3
Note:
1. If there is one or more 200 or higher indoor units within the same cooling system, and the number of indoor units exceeds 16 units, a
transmission booster is necessary (when a “PAR-F25MA Ver. F” or subsequent version of remote control is used).
2. If there is not even one 200 or higher indoor unit within the same cooling system, and the number of indoor units exceeds 20 units, a
transmission booster is necessary (when a “PAR-F25MA Ver. F” or subsequent version of remote control is used).
* For details, see wire connection example C.