MELSEC-F
SYSTEM CONFIGURATIONS2
2 - 3
(2) Connection using the 10BASE-T
Use devices that satisfy the standards of IEEE802.3 and 10BASE-T.
Shielded twisted pair cable (STP cable), category 3 (4, 5)
* Straight cables can be used.
(Correct operation is not guaranteed if a crossed cable is used to connect to
an external device via the 10BASE-T of the Ethernet module. However, it is
possible to use crossed cables to connect two Ethernet modules for data
communication or to connect an Ethernet module.)
•RJ45 plug
10Mbps hub
POINT
During the high-speed communication (100 M bps) via 100BASE-TX
connection, a communication error may occur due to the effect of high
frequency noise from devices other than PLC in a given installation
environment.The following describes countermeasures on the FX
3U-ENET-L
side to prevent the effect of high frequency noise for construction of a network
system.
(1) Wiring connection
Do not bundle the twisted pair cables with the main circuit and power wires,
and do not install them close to each other.
They should be installed at least 100 mm (3.94 in) away from each other.
Make sure to place the twisted pair cables in a duct.
(2) Communication method
Data communication with an external device is performed using TCP/IP
communication.
Increase the number of communication retries as necessary.
[When the error cannot be solved]
Communication is performed at a data transmission rate of 10 M bps by
changing the connection hub for the FX
3U-ENET-L to a hub capable of
handling 10 M bps.
External device
Twisted pair cable
Hub
* Up to 4 levels are allowed
for cascade connection
Ethernet module