Cornelius 10 Fan User Manual


 
5 300381000
INSTALLATION
This section covers unpacking and inspection, selecting location, installing Cooling Unit, preparing for operation,
and operation.
UNPACKING AND INSPECTION
NOTE: The Cooling Unit was thoroughly inspected before leaving the factory and the carrier has
accepted and signed for it. Any damage or irregularities should be noted at time of delivery (or not later
than 15 days from date of delivery) and immediately reported to the delivering carrier. Request a written
inspection report from Claims Inspector to substantiate any necessary claim. File claim with the
delivering carrier, not with IMI Cornelius Inc.
1. After Cooling Unit has been unpacked, remove shipping tape and other packing material.
2. Unpack LOOSE-SHIPPED PARTS. Make sure all items are present and in good condition.
Table 2. Loose-Shipped Parts
Item
No. Part No. Name Qty.
1 110085000 Tubing Clamp 2
2 111353000 Tubing Clamp 7
3 311962000 Label, Line Identification 1
NOTE: The following Remote Condenser Coil and Fan Assembly and Refrigeration Lines Kits are rec-
ommended for use with the Cooling
Units.
4 309602000 Remote Condenser Coil and Fan Assy 1
5 300598025 Refrigeration Line Kit, 25-ft. long, 90° 1
300598050 Refrigeration Line Kit, 50-ft. long, 90° Straight 1
IDENTIFICATION OF LOOSE-SHIPPED PARTS
1. TUBING CLAMPS (item 1) used to secure insulated python lines to Cooling Unit carbonated water outlet
lines.
2. TUBING CLAMPS (item 2) used to secure insulated python lines to Cooling Unit syrup and plain water
lines.
3. REFRIGERATION LINE KITS (item 5) is used to connect the REMOTE CONDENSER COIL AND FAN
ASSY (item 4) to the Cooling Unit.
SELECTING LOCATION
COOLING UNIT
Select location for Cooling Unit installation that will (1) Allow the shortest possible insulated python route from
the Cooling Unit to the Dispensing Station location; (2) Allow the shortest possible refrigeration lines (not to
exceed 50-ft in length) route from Remote Condenser Coil and Fan Assembly to the Cooling Unit; (3) REFER
TO THE COOLING UNIT NAMEPLATE FOR THE REQUIRED POWER CIRCUIT OPERATING VOLTAGE, HZ,
AND THE MINIMUM CIRCUIT AMPACITY OF THE COOLING UNIT. The power circuit for the Cooling Unit
must be wired through a 40-amp minimum rated disconnect switch (not provided) and the power circuit must be