Honeywell VISTA-20P Home Security System User Manual


 
UL NOTICES
1. Entry Delay No. 1 and No. 2 (fields
35,
36) cannot be greater than 30 seconds for UL
Residential Burglar Alarm installations, and entry delay plus dial delay should not
exceed 1 minute. For UL Commercial Burglar Alarm installations, total entry delay may
not exceed 45 seconds.
2. For UL Commercial Burglar Alarm (Grade AA) and UL Residential Burglar Alarm
installations with line security, total exit delay time must not exceed 60 seconds. For UL
Burglar Alarm installations without line security (Grade A), total exit delay time must
not exceed 120 seconds.
3. The maximum number of reports per armed period (field
93) must be set to “0”
(unlimited) for UL installations.
4. Periodic testing (see scheduling mode) must be at least every 24 hours.
5. Alarm Sounder plus Auxiliary Power currents must not exceed 600mA total for UL
installations (Aux power 500mA max.).
6. All partitions must be owned and managed by the same person(s).
7. All partitions must be part of one building at one street address.
8. If used, the audible alarm device(s) must be placed where it/they can be heard by all
partitions.
9. For UL commercial burglar alarm installations the control unit must be protected from
unauthorized access. The tamper switch installed to protect the control unit enclosure
door is suitable for this purpose.
10. Remote downloading without an alarm company technician on-site (unattended
downloading) is not permissible for UL installations.
11. Auto-disarming is not a UL Listed feature.
Notes for SIA Installations
1. As SIA limits for delay of alarm reporting and sounding can exceed UL limits for
commercial and residential applications, the following UL requirements per UL681 are
provided:
The maximum time that a control unit shall be programmed to delay the transmission of
a signal to a remote monitoring location, or to delay the energizing of a local alarm
sounding device to permit the alarm system user to enter and disarm the system, or to
arm the system and exit shall not exceed:
a) 60 seconds for a system with standard line security or encrypted line security,
b) 120 seconds for a system without standard line security or encrypted line security, or
c) 120 seconds for a system that does not transmit an alarm signal to a remote
monitoring location.
2. *34 Exit Delay: minimum exit delay is 45 seconds
3. *35/*36 Entry Delay 1 and 2: minimum entry delay is 30 seconds.
4. *39 Power Up in Previous State: must be “1,” power up in previous state
5. *40 PABX Access Code or Call Waiting Disable: If call waiting is used, call waiting
disable option in field *91 must be set.
6. *50 Burglary Dial Delay: delay must be minimum of 30 seconds.
7. *59 Exit Error Alarm Report Code: Always enabled.
8. *69 Recent Closing Report Code: Always enabled.
9. *91 Option Selection: Exit Delay option should be enabled. If call waiting is used, Call
Waiting Disable must be set to “1” (enabled).
10. *93 No. reports in Armed Period: Must be set for 1 or 2 report pairs.
Installation and Setup Guide
9-2