Honeywell VISTA-20P Home Security System User Manual


 
*32
Fire Alarm Sounder Timeout
0 = yes; sounder timeout after time selected in field
33
1 = no timeout; sounds until manually turned off
This control complies with NFPA requirements for
temporal pulse sounding of fire notification appliances.
Temporal pulse sounding for a fire alarm consists of the
following:
3 pulses – pause – 3 pulses – pause – 3 pulses.
UL fire alarm installations: must be 1.
*33
Alarm Sounder Timeout
0 = No timeout; 1 = 4 min; 2 = 8 min; 3 = 12 min; 4 = 16 min
This field determines whether the external sounder
will shut off after time allotted, or continue until
manually turned off.
UL Installations: For residential fire alarm
installation, must be set for a minimum of 4 min
(option 1); for UL Commercial Burglary installations,
must be minimum of 16 min (option 4).
*34
Exit Delay
00 - 96 = 0 - 96 seconds; 97 = 120 seconds
V20PSIA/V15PSIA: 45 - 96 = 45 - 96 secs; 97 = 120 secs
NOTE: Entries less than 45 will result in a 45-sec delay.
The system waits the time entered before arming
entry/exit zones. If the entry/exit door is left open after
this time expires, an alarm will occur. Common zones
use same delay as partition 1.
UL installations: For UL Commercial Burglar Alarm
(Grade AA) and UL Residential Burglar Alarm
installations with line security, total exit time must
not exceed 60 seconds. For UL Burglar Alarm
installations without line security (Grade A), total exit
time must not exceed 120 seconds.
SIA Guidelines: minimum exit delay is 45 seconds
*35
Entry Delay 1 (*35), Entry Delay 2 (*36)
*36
00 - 96 = 0 - 96 seconds; 97 = 120 secs; 98 = 180
secs; 99 = 240 secs
V20PSIA/V15PSIA: 30-96 = 30 - 96 secs;
97 = 120 secs; 98 = 180 secs; 99 = 240 secs
NOTE: Entries less than 30 will result in a 30-sec delay.
Upon entering, the system must be disarmed before
the time entered expires, otherwise it sounds an alarm.
Common zones use same delay as partition 1.
UL Installations: For UL Residential Burglary Alarm
installations, must be set for a maximum of 30 seconds;
entry delay plus dial delay should not exceed 1 min.
For UL Commercial Burglar Alarm, total entry delay
may not exceed 45 seconds.
SIA Guidelines: minimum entry delay is 30 seconds
*37
Audible Exit Warning
0 = no; 1 = yes
Warning sound consists of slow continuous beeps until
the last 10 seconds, and then it changes to fast beeps.
Sound ends when exit time expires.
SIA Guidelines: must be enabled (enter 1)
V20PSIA/V15PSIA: feature always enabled; field does
not exist.
*38
Confirmation Of Arming Ding
0 = no ding; 1 = confirmation ding after arming system
2 = ding after arming from RF button or RF keypad only
Confirmation of arming is 1/2-sec external sounder “ding.”
If 1 selected, ding occurs when closing report is sent, or
at the end of Exit Delay.
If 2 selected, ding occurs upon reception of the wireless
arming command.
UL Installations: must be 1 for UL Commercial
Burglar Alarm installations.
*39
Power-Up In Previous State
0 = always power-up in a disarmed state
1 = assume the system status prior to power down
When the system powers up armed, an alarm will
occur 1 minute after arming if a zone is faulted.
Note that if the previous state was armed Away or Stay,
the system will not respond to sensor changes for 1
minute, which allows sensors such as PIRs to stabilize.
UL Installations: must be 1 (power-up in previous state)
SIA Guidelines: must be 1
Dialer Programming (
40
50)
*40
PABX Access Code or Call Waiting Disable
Enter up to 6 digits if PABX is needed to access an
outside line. Do not fill unused spaces. 09, # + 11 for
,
# + 12 for #, # + 13 for a pause (2 seconds)
To clear entries from field, press 40. If fewer than 6
digits need to be entered, exit by pressing [].
Call Waiting: If the subscriber’s phone service has
“call waiting” (and is not using PABX), enter “*70” (“#
+ 11”) plus “# + 13” (pause) as the PABX entry to
disable “call waiting” during control panel calls. If the
subscriber does not have “call waiting” and is not using
PABX, make no entry in this field.
NOTES: 1. The call waiting disable feature cannot be
used on a PABX line. 2. Using Call Waiting Disable on
a non-call waiting line will prevent successful
communication to the central station.
V20PSIA/V15PSIA: If call waiting is used, enter call
waiting disable digits as described above, and also set Call
Waiting Disable option in field *91.
*41
Primary (*41) and Secondary (*42) Phone No.
*42
Enter up to 20 digits. 09, # + 11 =
, # + 12 = #,
# + 13 = pause (2 secs)
If entering fewer than 20 digits, exit by pressing [] +
next field number. To clear entries, press 41 or *42*
respectively. Do not fill unused spaces.
NOTE: Backup reporting (see field *49) is automatic
only if there is a secondary phone number (field 42).
*43
Primary/Secondary Account Numbers
*44
Enter 4 or 10 digits, depending on selection in
*45
*48 Report Format field. Enter 09; # + 11 = B,
*46
# + 12 = C, # + 13 = D, # + 14 = E, # + 15 = F.
*43: Partition 1 primary. To clear entries: 43.
*44: Partition 1 secondary. To clear entries: 44.
*45: VISTA-20P. Part. 2 prim. To clear entries: 45.
*46: VISTA-20P. Part. 2 second. To clear entries: 46.
Installation and Setup Guide
4-2