Honeywell THX9421 Thermostat User Manual


 
THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ 2.0 WITH EIM
33 68-0311—01
4130 Residential:
Entry / Exit Remote -
Away Heat Setpoint
Commercial:
Entry / Exit Remote -
Unoccupied Heat
Setpoint
None
40° F to 90° F
Note: setpoint is limited based on
setting at ISU 4100.
65° F Both No The thermostat maintains this Heat setting when the
user presses Away / Unoccupied at the Entry / Exit
Remote. Select None to delete this temperature
setting. The thermostat only responds to the Entry /
Exit Remote if a temperature is pre-set at this
screen. See “Wireless Entry/Exit Remote” beginning
on page 94.
4140 Residential:
Entry / Exit Remote -
Vacation Cool
Setpoint
Commercial:
Entry / Exit Remote -
Holiday Cool Setpoint
None
50° F to 99° F
Note: setpoint is limited based on
setting at ISU 4100.
82° F Both No The thermostat maintains this Cool setting when the
user presses Vacation / Holiday at the Entry / Exit
Remote. Select None to delete this temperature
setting. The thermostat only responds to the Entry /
Exit Remote if a temperature is pre-set at this
screen. See “Wireless Entry/Exit Remote” beginning
on page 94.
4140 Residential:
Entry / Exit Remote -
Vacation Heat
Setpoint
Commercial:
Entry / Exit Remote -
Holiday Heat Setpoint
None
40° F to 90° F
Note: setpoint is limited based on
setting at ISU 4100.
60° F Both No The thermostat maintains this Heat setting when the
user presses Vacation / Holiday at the Entry / Exit
Remote. Select None to delete this temperature
setting. The thermostat only responds to the Entry /
Exit Remote if a temperature is pre-set at this
screen. See “Wireless Entry/Exit Remote” beginning
on page 94.
5000 What Sensors are
WIRED to your
System?
Check box on screen for each:
Indoor Air Temperature
Outdoor Air Temperature
Return Air Temperature
Discharge Air Temperature
None Both Yes Wired Sensors requires an EIM (Equipment
Interface Module). This ISU is only displayed if an
S1 or S2 terminal is available.
Click boxes on screen to select which sensors are
wired to the S1 and S2 terminals at the EIM.
The thermostat will not display Outdoor Air
Temperature if a wireless outdoor air sensor is
connected.
The thermostat will not display Indoor Air
Temperature if 6 wireless indoor air sensors are
connected. If you have a wired Indoor Air
Temperature network (1, 4, 9 etc), the thermostat
will allow up to 5 wireless indoor air sensors.
The thermostat will not display Return / Discharge
Air Temperature if there is no fan in the system.
5010 Indoor Temperature
Sensor Name
[Sensor Name] Indoor Sensor Both Yes Wired Sensors requires an EIM (Equipment
Interface Module).
Enter a name (location) of the Wired Indoor Air
Temperature Sensor.
5020 What Terminals are
Wired to the Indoor
Temperature Sensor?
None
S1
S2
None Both Yes Wired Sensors requires an EIM (Equipment
Interface Module).
5030 Indoor Temperature
Sensor Type
10K
20K
10K:
if ISU 1010
Application is
Residential
20K:
if ISU 1010:
Application is
Commercial
Both Yes Wired Sensors requires an EIM (Equipment
Interface Module).
Select 10K or 20K based on the sensor installed.
Refer to resistance values below:
C7189U1005 = 10K ohm
C7772 = 20K ohm
TR21 = 20K ohm
TR21-A = 10K ohm (IMPORTANT - the TR21-A
must be used in combination with a TR21 sensor or
another TR21-A sensor for the thermostat to
calculate the correct indoor temperature reading).
See “Wiring guide — Wired Indoor Sensors”
beginning on page 119 for information on the
sensor type you should select based on how the
sensors are wired. For example, you would select
20K when you have two TR21-A (10K) sensors
wired in series.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number Installer Setup Name Settings Default
Residential,
Commercial
or Both
Requires
EIM Notes