THX9321 PRESTIGE
®
2.0 AND THX9421 PRESTIGE
®
IAQ 2.0 WITH EIM
57 68-0311—01
3. Press Search by Event to search for specific user inter-
actions.
Fig. 78.
4. Select the desired user interactions and press Done.
TO SAVE A DATA LOG TO A MEMORY STICK
1. Insert memory stick in thermostat USB port.
2. The USB options will be displayed.
Fig. 79.
3. Press Data Logs.
4. Select the log you want to save to USB.
Fig. 80.
5. When you plug the memory stick into a computer, you
can view Data Log information in a spreadsheet.
ADVANCED DATA LOG OPTIONS
You can turn the Data Logs off or Delete/Reset them from this
screen.
1. Follow the steps in “Using the Data Logs” beginning on
page 56. Press the Advanced Options button.
Fig. 81.
2. Change the settings and press Done.
Dry Contact Alerts
If you are not using S1 and S2 terminals on the EIM for Delta T
Diagnostics, you can connect them to a dry contact device to
display an alert.
NOTE: You can connect multiple Dry Contact devices in
parallel to the S1 or S2 terminals.
When the dry contact device detects a problem, the thermostat
displays an alert on the home screen along with the dealer
information. See Fig. 82 as an example.
Fig. 82.
When the user presses the alert for more info, the Notification
screen is displayed, prompting them to contact their dealer.
See Fig. 83 as an example.
Fig. 83.