Honeywell S7999B Boiler User Manual


 
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE
59 65-0303—05
Pilot test hold On
Off
29 32
Ignition
source
Hot Surface Igniter
External ignition
Internal ignition
Pilot type Direct burner constant ignition
Direct burner pulsed ignition
Intermittent
Interrupted
Lightoff rate RPM or %
Preignition
time
0-600 seconds
0 = Not configured
Pilot Flame
Establishing
Period
15 secs
10 secs
4 secs
Igniter on
during
1st half of PFEP
Pilot Flame Establishing Period
Main Flame
Establishing
Period
15 secs
10 secs
5 secs
Flame
Threshold
μA/V
Ignite failure
response
Lockout
Recycle
Recycle & hold
Recycle & lockout
30 32
Ignite failure
delay
0-600 seconds
0 = Not configured
Ignite failure
retries
1, 3, or 5
MFEP flame
failure
response
Recycle
Lockout
Run flame
failure
response
Recycle
Lockout
Fan speed
error
response
Recycle
Lockout
Table 61. Configurable Parameters. (Continued)
Parameter Comment
Table
#
Page
#
Flame sensor
type
Flame rod
UV power tube
UV power tube with spark
interference
None
31 35
Modulation
output
4-20mA
0-10V
Fan PWM*
Blower/HSI Blower
Hot surface ignition
Temperature
units
Fahrenheit
Celsius
Anti short-
cycle time
0-600 seconds
0 = Not configured
Alarm silence
time
0-600 minutes
0 = Not configured
Power up
with Lockout
Clear lockout
Do NOT clear lockout
STAT &
EnviraCOM
remote stat
Enabled
Disabled
Flame sensor
type
Flame rod
UV
32 35
Modulation
output
4-20ma
0-10V
Fan PWM
Blower/HSI Blower
Hot surface ignitor
Temperature
units
Fahrenheit
Celsius
Anti short
cycle time
0-600 minutes
Alarm silence
time
0-600 minutes
Power up
with lockout
Clear lockout
Do NOT clear lockout
Inlet
connector
type
0-15 psi
0-150 psi
UNCONFIGURED
Stack
connector
type
10k NTC dual safety
10k NTC single non-safety
12k NTC single non-safety
UNCONFIGURED
Header 4-20ma
UNCONFIGURED
Table 61. Configurable Parameters. (Continued)
Parameter Comment
Table
#
Page
#