After successful login, the user presses the Begin button to
start safety parameter verification. See Fig. 59.
Fig. 59. Begin safety verification.
The first group of safety configuration parameters that needs
verification is displayed. The user is asked to confirm that the
settings are correct, as shown in Fig. 60.
Fig. 60. Confirm safety parameter settings.
After the first safety parameter group has been confirmed by
the user (by pressing the Yes button), the next safety
parameter group waits for verification as shown in Fig. 61.
Fig. 61. Safety parameter settings confirmed; next group
waiting for confirmation.
The user has 30 secs to confirm each safety configuration
group’s settings. If the user takes too long to confirm the
settings, an error message is displayed, as shown in Fig. 62.
Fig. 62. Confirmation timed out.
After all safety parameter groups have been verified, the user
must press the Reset button on the control within 30 seconds
to confirm the correct device. See Fig. 63.