Honeywell S7999B Boiler User Manual


 
S7999B, S7999C SOLA LOCAL OPERATOR INTERFACE
57 65-0303—05
DHW high
limit
Enabled
Disabled
19 27
DHW high
limit
response
Suspend DHW
Recycle & hold
Lockout
DHW high
limit setpoint
-40 °F to 266 °F
(-40 °C to 130 °C)
Outlet high
limit
response
Recycle & hold
Lockout
Outlet high
limit setpoint
-40 °F to 266 °F
(-40 °C to 130 °C)
Stack limit Enabled
Disabled
20 28
Stack limit
delay
0-600 seconds
Stack limit
response
Lockout
Recycle & delay
Stack limit
setpoint
-40 °F to 266 °F
(-40 °C to 130 °C)
Delta T
enable
Enabled
Disabled
21 28
Delta T
degrees
-40 °F to 266 °F
(-40 °C to 130 °C)
Delta T delay 0-600 seconds
Delta T
response
Recycle & delay
Lockout
Delta T retry
limit
Delta T rate
limit enable
Enabled
Disabled
Delta T
inverse limit
time
___hour ___min ___sec
Delta T
inverse limit
response
Recycle & delay
Recycle & delay with retry limit
Lockout
Outlet T-rise
enable
Enabled
Disabled
22 29
Heat
exchanger T-
rise enable
Enabled
Disabled
T-rise
degrees
0 °F to 234 °F
(-17 °C to 112 °C)
T-rise
response
Recycle & delay
Recycle & delay with retry limit
Lockout
T-rise retry
limit
0 to 100
T-rise delay ___hour ___min ___sec
Table 61. Configurable Parameters. (Continued)
Parameter Comment
Table
#
Page
#
Heat
exchanger
high limit
enable
Enabled
Disabled
23 29
Heat
exchanger
high limit
setpoint
-40 °F to 266 °F
(-40 °C to 130 °C)
Heat
exchanger
high limit
response
Recycle & delay
Recycle & delay with retry limit
Lockout
Heat
exchanger
retry limit
0 to 100
Heat
exchanger
high limit
delay
___hour ___min ___sec
CH anticon-
densation
enable
Enabled
Disabled
24 29
CH anticon-
densation
pump
Normal (no change)
CH pump forced off
CH anticon-
densation
setpoint
-40 °F to 266 °F
(-40 °C to 130 °C)
DHW anti-
condensa-
tion enable
Enabled
Disabled
DHW anti-
condensa-
tion pump
Normal (no change)
DHW pump forced off
DHW anti-
condensa-
tion setpoint
-40 °F to 266 °F
(-40 °C to 130 °C)
Anticondensa
tion Priority
Anticondensation is more
important than (check those
that apply):
Stack limit
Delta T limit
Slow start
Forced rate
Outlet high limit
Table 61. Configurable Parameters. (Continued)
Parameter Comment
Table
#
Page
#