2. CONFIGURATION
2.1 Adding a device
Use this page to add an Stryker VAV device to the LON network. You can add a device either in the online mode or the offline
mode.
To add an Stryker VAV device:
2.2 Configuring the Stryker VAV Device
Use this page to configure an Stryker VAV device on the LON network. You can configure the device either in the online mode or
the offline mode.
To configure the Stryker VAV device:
2.3 Fields
Step Action
1 From the Lon Device Manager, click New. The New dialog box appears.
2 Select AscLonVAV Device from the Type to Add list.
3 Type one in the Number to Add box. Click Ok. The details of the device are displayed.
4 Enter information in the available fields.
5
Click Ok. You can view the newly added device under Local Lon Device items in the Nav palette.
Note: The other way to add a new device is by using the Lon Discover option.
Step Action
1
From the Nav menu, choose Station > Driver > LON network > AscLonVAV device.
2
Double click AscLonVAVDevice. The VAV Configuration Wizard page appears.
3
Enter information in the available fields.
4
Click Next to display the Outputs page.
5
Click UndoAll to revert to the last saved settings.
6
Click Finish to save settings to station.
Table 3. Stryker VAV Device Fields.
Name Definition
Controller Type Displays the Controller Type such as With Actuator or Without Actuator.
Pressure Type Displays the VAV Terminal Unit pressure control operation for this application. This selection defines
how the controller will operate the VAV Terminal Units damper. Valid selections for this field are:
Pressure Independent - The controller uses airflow as the primary means of controlling the VAV
Terminal Damper.
Pressure Dependent - The controller uses space temperature as the primary means of controlling
the VAV Terminal Damper.
Box Type Displays the physical type of VAV Terminal. This selection determines what control options are
available for the VAV Terminal. Valid selections for this field are:
Single Duct: This VAV Terminal type consists of a single primary air supply inlet connection with or
without a primary flow sensor. This box type is primarily used for cooling only applications, cooling
with local reheat or dual temperature (central heating/cooling) systems.