3.1 Fields
Table 4. Output Fields.
Name Definition
Output Displays the list of Outputs that can be controlled such as: Damper motor, Reheat, Peripheral heat,
Fan and Wall module occupancy status LED.
Output Assignment Displays the mode of output assignment for all output types.
Damper Motor: Enables you to select the damper motor control type as Analog Control, PWM
Control, and Floating Control.
NOTE: Floating actuators are recommended for pressure independent control since the Ana-
log or PWM type of actuators do not provide the required resolution for achieving sta-
ble flow.
Reheat: This enables you to configure modulating reheat or upto 3 stages of reheat.
NOTE: Damper is controlled during reheat based on the 'Modulate Reheat Flow' configura-
tion. This is available under 'Output parameters' for Reheat
Peripheral Heat: This enables you to configured staged or modulating control of peripheral heat.
NOTE: When both Reheat and peripheral heat are configured, the sequence of control is
determined by the 'Heating sequence' configuration under Output Parameters. When
modulating control is selected for peripheral heat, the minimum peripheral heat modu-
lating valve position can be configured under Ouput Parameters.
Fan: Enables you to select the fan types such as No Fan, Series Fan, Parallel Temperature Control,
Parallel Flow Control, Parallel PWM Control fan, and Parallel speed control for float and analog.
Wallmodule Occupancy Status LED: This output controls the LED available on the TR21-series
wallmodules.
Additional Outputs: The following optional outputs can be configured:
Auxiliary Digital Output: This output is activated when the effective occupancy is 'Occupied'.
Auxiliary Pulse On: This output is pulsed when the effective occupancy changes to 'Occupied'.
Auxiliary Pulse Off: This output is pulsed when the effective occupancy changes to 'UnOccupied'.
Free Digital Output, Free Pulse On and Free Pulse Off: These outputs are controlled from the
network through nviFree1Dig.
Free Analog output: This output is controlled from the network through nviFree1Mod.
Output Name Enables you to edit the default output name.
NOTE: A maximum length of 18 characters is allowed. The following characters are valid a-z,
A-Z, 0-9, under-score and space.