STRYKER VAV USER GUIDE
62-2030—01 24
15.1 Fields
NOTE: Note: Only configurable parameters are dis-
played in the Monitoring screen.
NOTE: Note: For the Monitor Sensor input the value will
be displayed as reported from the controller even
if the value lies outside the range of the sensor
type that is configured. If the value reported from
the controller is +inf or –inf or NaN then the text
Invalid will be displayed.
The list of configurable parameters is
• Temporary set point
• Effective temperature set point
• Scheduled Occupancy
• Sensed Occupancy
• Effective Occupancy
• Manual Occupancy
• Application Mode
•Box Flow
• Damper Position
• Fan Speed
• Fan Status
• Heating Stages On
• Reheat percentage
• DLC shed status
• Space Temperature
• Supply Temperature
• Discharge Air
• Peripheral Heat
• Outdoor air temperature
• Monitor Switch
• Free Digital Output
• Window Open
• Heat Cool Switch
• Auxiliary Digital Output
• Free 1 Modulating
• Monitor Sensor
• Space CO2
• Space Relative humidity
Related Topics
“1. About Stryker VAV” on page 2
“2. Configuration” on page 4
Table 14. Monitoring Fields.
Name Definition
Name Displays the configured parameter names.
Read Value Displays the current value read from the controller.
Write Value Enables you to write the expected value to the controller.
Current Mode Displays the current mode of the controller.
Units Displays the respective units of the parameters.
Current Mode This fields displays whether the controller is in manual control or in auto mode.
Temperature set point You can temporarily change/override the setpoint using this field. Enter the setpoint value and
click the Write button at the bottom of the screen. To remove the temporary override, type 'Nan'
in this field and click the Write button.
Application Mode This field can be used to switch between off, auto, heating and cooling. The following options
can be selected.
Auto - Enable this option for auto reheating and cooling
Heat - Enable this option to supply warm air and reheat
Morning warmup - Enable this option to supply warm air and to trigger reheat as per the
'Morning warmup type' configured.
Cool - Enable this option to supply cool air and lock reheat. Use this mode to disable reheat
when boiler hot water is unavailable.
Night purge - Enable this option to supply outdoor air.
Off - Enable this option to off fan, heating and cooling.
Fan only - Enable this option to enable only fan, no heating or cooling.
Note that all other options are ignored by the controller.