Honeywell 62-2030-01 Furnace User Manual


 
STRYKER VAV USER GUIDE
17 62-2030—01
RELATED TOPICS
“1. About Stryker VAV” on page 2
“2. Configuration” on page 4
10. CONFIGURING THE ACCESSORY LOOPS
Use this page to configure accessory loops for Stryker VAV device on the LON network.
To configure Accessory Loops:
10.1 Fields
Heating Integral Time Value must be configured based on reheat configuration.
Heating Derivative
Time
Value must be between 0 to 9000 sec.
Table 10. PID Names. (Continued)
Name Definition
Reheat Type Integral Time (sec)
modulating 2400
1 stage 3100
2 stage 2500
3 stage 1650
4 stage 1200
Step Action
1 From the left pane of the VAV Configuration Wizard, select Accessory Loops.
The Loop1 page appears.
2 Enter information in the available fields.
3 From the menu bar, click Loop2. The Loop2 page appears.
4 Enter information in the available fields.
5 Click Next to display the Custom wiring page.
6 Click Undo All to revert to the last saved settings.
7 Click Finish to save settings to station.
Table 11. Accessory Loop Fields.
Name Definition
Loop Name Enter a custom name for the loop.
NOTE: A maximum length of 18 characters is allowed. The following characters are valid
a-z, A-Z, 0-9, under-score and space.
Outputs Accessory loop can be configured to drive a modulating output, upto 3 staged outputs and an
auxiliary digital output. The outputs can be configured only when the required pins are available/
free. Please refer the "3. Configuring the Outputs" section to configure output parameters.
Staged Control action: Staged outputs can be configured with either as conventional staged
outputs or as staged outputs with thermostat using 3 Cycles per Hour.
Inputs Please refer the "4. Configuring the Inputs" section.
To use shared inputs:
Select the Shared Input from the Input Name drop down list.
To use main application output as an input:
Select the Main Application from the Input name drop down list.