Heat & Glo LifeStyle XLR-PB-AU Indoor Fireplace User Manual


 
51Heat & Glo • XLR-N-AU, XLR-PB-AU • 2198-906 Rev. M • 5/12
Non-Combustible Finish Material 0 - 4 in. (0 - 102 mm) Thick
Bottom Joint
3/4 in (19 mm)
3 in. (76 mm)
3/4 in (19 mm)
Figure13.14NoncombustibleSurfaceFinishingMaterial
0-4in.(0-102mm)Thick-InsideFitMethod
(TonicDecorativeFrontOnly)
FACTORY-INSTALLED
NON-COMBUSTIBLE
BOARD
\\\
\\\
\\\
\\\
\\\
\\\
\\\
\\\
\\\
\\\
\\\
\\\
\\\
\\\
\\\
\\\
\\\
\\\
\\\
\\\
\\\
\\\
\\\
\\\
\\\
\\\
DRYWALL OR
EQUIVALENT
3/8 in. (10 mm)
20-1/2 in. (520 mm)
APPLIANCE
OPENING (HEIGHT)
3/4 in.
(19 mm)
3 in. (76 mm)
0-4 in.
(0-102 mm)
0-4 in.
(0-102 mm)
Figure13.13InsideFitMethod(TonicDecorativeFrontOnly)
Non-CombustibleFinishMaterials
0in.to4in.(0mmto102mm)ThickInsideFitMethod
The Tonic decorative front is approved for inside t ap-
plications. Non-combustible nishing materials up to 4
in. (102 mm) thick can be installed around the front (left,
right, top, and bottom).
For the Tonic decorative front inside t applications, the
decorative front must be installed tight to the nishing
anges and must not overlap any nish material.
Ensure that no non-combustible nish materials are in-
stalled within 3/4 in. (19 mm) of the replace opening.
The 3/4 in. (19 mm) spacing is required to provide clear-
ance for removing and installing the Tonic decorative
front. See Figure 13.14.