Heat & Glo LifeStyle XLR-PB-AU Indoor Fireplace User Manual


 
41Heat & Glo • XLR-N-AU, XLR-PB-AU • 2198-906 Rev. M • 5/12
K. InstallHorizontalTerminationCap
WARNING! Risk of Fire! The telescoping ue section
of the termination cap MUST be used when connecting
vent.
• 1-1/2 in. (38 mm) minimum overlap of ue telescoping
section is required.
Failure to maintain overlap may cause overheating and
re.
• Vent termination must not be recessed in the wall. Siding
may be brought to the edge of the cap base.
• Flash and seal as appropriate for siding material at
outside edges of cap.
• When installing a horizontal termination cap, follow the
cap location guidelines as prescribed by current local or
national codes and refer to Section 6 of this manual.
CAUTION! Risk of Burns! Local codes may require in-
stallation of a cap shield to prevent anything or anyone
from touching the hot cap.
Note:When using termination caps with factory-supplied heat
shield attached, no additional wall shield restop is required on
the exterior side of a combustible wall.
Figure10.17VentingthroughtheWall
• The termination kit should pass through the wall restops
from the exterior of the building.
• Adjust the termination cap to its nal exterior position on
the building and interlock the ue sections.
WARNING! Risk of Fire! the termination cap must be
positioned so that the arrow is pointing up.
• Use a high-temperature sealant gasket to seal between
the pipe and exterior restop.
EXTERIOR
INTERIOR
Interior
Wall Shield
Inner Flue
Rear Flue
Heat Shield
1-1/2 in. (38 mm)
min.
overlap
Outer Flue
Figure10.18TerminationCap
1 in. (25 mm)
7-1/2 in.
(192 mm)
MINIMUM