Heat & Glo LifeStyle ESC-42ST Indoor Fireplace User Manual


 
Heat & Glo • ESC-42ST • 2146-900 Rev. o • 5/12 29
2. Top Vent - Vertical Termination
No Elbow
Figure 7.6
V
1
V
1
= 50 ft. Max. (15.2 m)
V
1
= 3 ft. Min. (914 mm)
Figure 7.7
V
1
H
1
V
2
2 ft 610 mm 1 ft 305 mm *
3 ft 914 mm 3 ft 914 mm *
4 ft 1.2 m 4 ft 1.2 m *
5 ft 1.5 m 9 ft 2.7 m *
6 ft 1.8 m 12 ft 3.7 m *
V
1
+ V
2
+ H
1
= 50 ft (15.2 m) Max.
*No speci c restrictions on this value EXCEPT
V
1
+ V
2
+ H
1
cannot exceed 60 ft (18.3 m).
After V
1
= 6 ft, then H
1
Max.= V
1
x 2
FLUE RESTRICTOR
NOTE: Flue Restrictor ships in
manual bag assembly.
Note: Flue restrictor is permit-
ted ONLY on 30 ft. minimum
vertical runs with no elbows.
Note: Must have a 24 inches minimum
vertical vent before attaching any
elbow to the appliance.
Note: Flue restrictor is permit-
ted ONLY on 30 ft. minimum
vertical runs with no elbows.
Note: Must have a 24 inches minimum
vertical vent before attaching any
elbow to the appliance.