Heat & Glo LifeStyle ESC-42ST Indoor Fireplace User Manual


 
Heat & Glo • ESC-42ST • 2146-900 Rev. o • 5/12 27
H
2
H
1
V
1
INSTALLED
HORIZONTALLY
1. Top Vent - Horizontal Termination
V
1
H
1
Figure 7.3
Figure 7.4
1. Top Vent - Horizontal Termination
One Elbow
Two Elbows
Fire Risk. Explosion Risk.
Do NOT pack insulation or other combustibles between ceiling restops.
ALWAYS maintain speci ed clearances around venting and restop systems.
Install wall shield and ceiling restops as speci ed.
Failure to keep insulation or other material away from vent pipe may cause re.
WARNING
V
1
Minimum H
1
Maximum
2 ft 610 mm 7 in* 178 mm
3 ft 914 mm 2 ft 610 mm
4 ft 1.2 m 4 ft 1.2 m
5 ft 1.5 m 9 ft 2.7 m
6 ft 1.8 m 12 ft 3.7 m
7 ft 2.1 m 14 ft 4.3 m
10 ft 3.0 m 20 ft 6.1 m
20 ft 6.1 m 40 ft 12.2 m
After V
1
= 6 ft then H
1
= 2 x V ft Maximum
V
1
+ H
1
= 60 ft Maximum
*when used with approved termination caps
V
1
Minimum
H
1
+ H
2
3 ft 914 mm 18 in 457 mm
4 ft 1.2 m 3 ft 914 mm
5 ft 1.5 m 7 ft 2.1 m
6 ft 1.8 m 10 ft 3.0 m
7 ft 2.1 m 12 ft 3.7 m
10 ft 3.0 m 18 ft 5.5 m
20 ft 6.1 m 20 ft 6.1 m
After V
1
= 6 ft then H
1
= 2 x V
1
ft Maximum
V
1
+ H
1
+ H
2
= 60 ft Maximum
H
1
+ H
2
= 20 ft Maximum
Note: Must have a 24 inches minimum
vertical vent before attaching any
elbow to the appliance.
Note: Flue restrictor is permit-
ted ONLY on 30 ft. minimum
vertical runs with no elbows.
Note: Flue restrictor is permit-
ted ONLY on 30 ft. minimum
vertical runs with no elbows.
Note: Must have a 24 inches minimum
vertical vent before attaching any
elbow to the appliance.