Heat & Glo LifeStyle 6000GCF-IPILP Indoor Fireplace User Manual


 
Heat & Glo • 6000GCF-IPI, 6000GCF-IPILP • 2110-900 Rev. F • 6/08 17
A. Pipe Clearances to Combustibles
6
6
Vent Clearances and Framing
Fire Risk.
Explosion Risk.
Maintain vent clearance to combustibles as
speci ed.
• Do not pack air space with insulation or
other materials.
Failure to keep insulation or other materials
away from vent pipe may cause re.
Figure 6.1 Pipe Clearances
1 in. CLEARANCE
AROUND VERTICAL
SECTIONS
3 in. TOP
CLEARANCE
1 in. SIDE AND
BOTTOM CLEARANCE
WARNING
COMBUSTIBLE SURFACE
DIRECTION
UP
HEAT SHIELD
90º ELBOW
Figure 6.2
Figure 6.3
CORRECT INCORRECT
Fasten the shield in place using the four pilot holes pro-
vided in the part.
Position the shield so the longest dimension (13 1/2 inch)
is placed in same direction the elbow is pointing.
• Center the shield directly above the elbow with a 1/2
inch air space between shield and combustible surface
(see Figure 6.3).
HEAT
SHIELD
3 IN MIN.
(76 mm)
COMBUSTIBLE
SURFACE
WARNING
Fire Risk.
Installation of this appliance may require the
use of heat shield 385-920 above the rst 90º
elbow in the venting system.
• Heat shield required if vertical distance between top of
horizontal elbow and any combustible surface above elbow
is less than 4 inches.
• Heat shield not required if distance is more than 4
inches.
Attach elbow heat shield to the exhaust pipe if combusti-
ble materials are not present at install (see Figure 6.4).
Cut the tabs as shown and bend down. Using the screws
found in the manual bag secure the heat shield to the pipe
maintaining 3 to 4 inches between the pipe and shield.
SCREW
3 in.
(76 mm)
Figure 6.4